Mechanical Vibration Specifications; Xp24000/Xp20000 Ac Line Voltage Requirements; Xp24000 Dkc Power Specifications For 50-Amp, 50 Or 60 Hz, Single-Phase; Xp24000 Dkc Power Specifications For 30-Amp, 50 Or 60 Hz, Single-Phase - HP StorageWorks XP20000/XP24000 - Disk Array Owner's Manual

Hp storageworks xp24000/xp20000 disk array owners guide (ae131-96072, december 2009)
Hide thumbs Also See for StorageWorks XP20000/XP24000 - Disk Array:
Table of Contents

Advertisement

Humidity range type
Shipping and storage humidity range (product packed in factory packing)

Mechanical vibration specifications

Maximum operating acceleration is 0.05G at a frequency range of 10 to 300 Hz.

XP24000/XP20000 AC line voltage requirements

Each DKC or DKU has two or four power cords. In case of a failure of the power source for one cord,
the power requirements, and therefore the current requirement for the remaining power cord, will
double.
For details about cabling and connectors, current requirements, and other electrical specifications,
see the HP StorageWorks Disk Array Site Preparation Guide.
Table 8 XP24000 DKC power specifications for 50-amp, 50 or 60 Hz, single-phase
Parameter
Number of
power cords
Recommended
circuit breakers
Number of
circuit breakers
Table 9 XP24000 DKC power specifications for 30-amp, 50 or 60 Hz, single-phase
Parameter
Number of
power cords
Recommended
circuit breakers
32
Hardware description of the HP XP24000/XP20000 Disk Array
200 VAC
208 VAC
50/60 Hz
60 Hz
2
2
50A
50A
2
2
200 VAC
208 VAC
50/60 Hz
60 Hz
4
4
30A
30A
Noncondensing relative humid-
ity (RH)
5% to 95%
220 VAC
230 VAC
50 Hz
50/60 Hz
2
2
50A
50A
2
2
220 VAC
230 VAC
50 Hz
50/60 Hz
4
4
30A
30A
240 VAC
50 Hz
2
50A
2
240 VAC
50 Hz
4
30A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Storageworks xp24000Storageworks xp20000

Table of Contents