50-Amp, Single-Phase Power Cords; Fault-Tolerant Wiring With 50-Amp, Single-Phase Power Cords; Fault-Tolerant Wiring With 30-Amp, Single-Phase Power Cords - HP StorageWorks XP12000 - Disk Array Site Preparation Manual

Disk array
Hide thumbs Also See for StorageWorks XP12000 - Disk Array:
Table of Contents

Advertisement

50-amp, single-phase power cords

Each 50-amp XP12000 disk array rack has two power supply cords with attachment plug type
Russellstoll 9P53U2.
Figure 12 Fault-tolerant wiring with 50-amp, single-phase power cords
Be sure to install Russellstoll 9C53U2 or 9R53U2W socket receptacles between the power distribution
panel of the building and the power plugs for the unit.
The power cords provided with the disk array are nonshielded, type ST or equivalent with three #6
AWG (minimum) conductors terminated at one end with an assembled 9C53U2 plug connector.
30-amp, single-phase power cords
Each 30-amp HP XP12000 disk array rack has four power supply cords with attachment plug type
Russellstoll 3750DP.
Figure 13 Fault-tolerant wiring with 30-amp, single-phase power cords
Be sure to install Russellstoll 3933 (alternate, 9C33U0) or 3753 (alternate, 9R33U0W) socket
receptacles between the power distribution panel of the building and the power plugs for the unit.
XP12000 Disk Array Site Preparation Guide
55

Advertisement

Table of Contents
loading

Table of Contents