GOLD CGs Gas-Fired Water Boiler — Boiler Manual
7b
Start-up — operate boiler
If you discover evidence of any gas leak, shut down the
boiler at once. Find the leak source with bubble test and
repair immediately. Do not start boiler again until cor-
rected. Failure to comply could result in severe personal
injury, death or substantial property damage.
Check burner flames
View pilot and main flames through the inspection port
in the Air inlet box front cover.
Pilot burner flame (
PROPER pilot flame characteristics
1. Blue flame.
. Inner cone engulfing pilot flame sensor.
3. Pilot flame sensor glowing cherry red.
IMPROPER pilot flame characteristics:
1. Overfired — Large flame lifting or blowing past pilot
flame sensor.
. Underfired — Small flame. Inner cone not engulfing
pilot flame sensor.
3. Lack of primary air — Yellow flame tip.
4. Incorrectly heated pilot flame sensor.
Main burner flame (
PROPER main burner flame characteristics
1. Yellow-orange streaks may appear (caused by
dust).
IMPROPER main burner flame characteristics
1. Overfired — Large flames.
. Underfired — Small flames.
3. Lack of primary air — Yellow tipping on flames
(sooting will occur).
7c
Start-up — if boiler doesn't start . . .
Check for:
1. Loose connections, blown fuse or service switch
off?
. High limit switch set below boiler water tempera-
ture?
3. Thermostat set below room temperature?
4. Gas not turned on at meter or boiler?
Part number 550-110-260/0107
Figure 16
)
Figure 17
)
(continued)
Figure 16 Typical pilot burner flame
Figure 17 Typical main burner flame
5. Incoming gas pressure less than:
5" w.c. for natural gas?
11" w.c. for propane gas?
6. If none of the above corrects the problem, refer to
Troubleshooting
, Section
11
of this manual.
9