Remote Control; Remote Wall Switch; Wall Thermostat - UltraGlow G33R-NG1 Natural Gas Owners & Installation Manual

Zero clearance rear direct vent gas fireplace
Table of Contents

Advertisement

Option 1:

REMOTE CONTROL

Use the Regency Remote Control Kit approved
for this unit. Use of other systems may void
your warranty.
The remote control kit comes with a hand held
transmitter, a receiver and a wall mounting
plate.
1) Choose a convenient location on the wall
to install the receiver and the receptacle
box (protection from extreme heat is very
important). Run wires from the fi replace to
that location. Use Thermostat Wire Table.
2) Connect the two wires to the gas valve. See
diagram below.
CAUTION
Do not wire millivolt
remote control wires
to a 120V wire.
3) Install 3 AAA alkaline batteries in transmitter
and 4 AA alkaline batteries in the receiver.
Install the receiver and its cover in the wall.
Switch the
remote receiver to "remote"
mode. The remote control is now ready for
operation.
UltraGlow G33R-1 Zero Clearance Rear Vent Direct Vent Gas Fireplace
Option 2:
WALL SWITCH
1) Run the supplied wire through the right or
left side inlet opening. Be careful not to
damage the wire.
Note: We recommend a maximum of 15'
of wire but if you wish to go with a
longer run, use the Thermostat Wire
Table.
2) Connect the wire to the supplied wall switch
and install into the receptacle box.
CAUTION
Do not wire millivolt
wall switch wire
to a 120V wire.
INSTALLATION
Option 3:

WALL THERMOSTAT

A wall thermostat may be installed if desired,
connect the wires as per the wiring diagram.
Use table below to determine the maximum
wire length.
Note: Preferable if the thermostat is in-
stalled on an interior wall.
Regency offers an optional programmable
thermostat but any 250-750 millivolt rated non-
anticipator type thermostat that is CSA, ULC or
UL approved may be used.
CAUTION
Do not wire millivolt
wall thermostat wires
to a 120V wire.
Caution: Ensure that the wires do
not touch any hot surfaces and are
away from sharp edges.
Thermostat Wire Table
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System)
Wire Size
Max. Length
14 GA.
50 Ft.
16 GA.
32 Ft.
18 GA.
20 Ft.
20 GA.
12 Ft.
22 GA.
9 Ft.
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G33r-lp1G33r

Table of Contents