Greenheck Vektor-H Installation, Operation And Maintenance Manual

Greenheck Vektor-H Installation, Operation And Maintenance Manual

Laboratory exhaust system

Advertisement

®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble,
install, operate or maintain the product described. Protect yourself and others by observing all safety
information. Failure to comply with instructions could result in personal injury and/or property damage!
®
Vektor
-H

Table of Contents

General Safety Information . . . . . . . . . . . . . . . . . . . . . .1
Removing from Storage . . . . . . . . . . . . . . . . . . . . . . .3
Unit and System Identification . . . . . . . . . . . . . . . . . .3
Pre-Installation Information . . . . . . . . . . . . . . . . . . . .3
Electrical Disconnects . . . . . . . . . . . . . . . . . . . . . . . .3
Moving Parts / Guards . . . . . . . . . . . . . . . . . . . . . . . .3
Air Pressure and Suction . . . . . . . . . . . . . . . . . . . . . .3
Lifting Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Roof Curb and Mounting Details . . . . . . . . . . . . . . . . .4
Duct Installation - Bottom Inlet . . . . . . . . . . . . . . . . . .5
Side or End . . . . . . . . . . . . . . . . . . .5
Stack Extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
System Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Kitchen Roof Mounting Installation . . . . . . . . . . . . . . . .6
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . .7
Variable Frequency Drive . . . . . . . . . . . . . . . . . . . . . . .8
Pre-Start-Up Checks . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Belts / Fasteners and Set Screws . . . . . . . . . . . . . . .9
Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Fan Shaft Bearings . . . . . . . . . . . . . . . . . . . . . . . . . .9
Bearing Relubication Schedule . . . . . . . . . . . . . . . .10
Vektor-HS Nozzle Bearings . . . . . . . . . . . . . . . . . . .10
Damper Actuators . . . . . . . . . . . . . . . . . . . . . . . . . .10
Parts List and Assembly . . . . . . . . . . . . . . . . . . . . . . .11
Maintenance Log . . . . . . . . . . . . . . . . . . . . . . Backcover
Our Commitment . . . . . . . . . . . . . . . . . . . . . . Backcover
®
®
Vektor
-HS
Model Vektor
Laboratory Exhaust System

General Safety Information

Only qualified personnel should install this fan system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if high winds or seismic
activity are present. If more information is needed,
contact a licensed professional engineer before moving
forward.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC), the National Fire
Protection Agency (NFPA), where applicable. Follow
the Canadian Electrical Code (CEC) in Canada.
2. The rotation of the wheel is critical. It must be free
to rotate without striking or rubbing any stationary
objects.
3. Motor must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan rpm. Adjustments to fan speed
significantly effects motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to a duct while the fan is
running.
DANGER
Always disconnect power before working on or near a
fan. Lock and tag the disconnect switch or breaker to
prevent accidental power up.
CAUTION
When servicing the fan, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
Document #469003
®
-H and Vektor
®
-HS
Laboratory Exhaust System
1

Advertisement

Table of Contents
loading

Summary of Contents for Greenheck Vektor-H

  • Page 1: Table Of Contents

    Document #469003 Model Vektor ® -H and Vektor ® Laboratory Exhaust System ® Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information.
  • Page 2: Receiving / Unpacking / Handling / Storage

    Receiving Remove any accumulations of dirt, water, ice or snow and wipe dry before moving to indoor storage. To avoid Greenheck model Vektor-H and Vektor-HS fans are “sweating” of metal parts allow cold parts to reach room thoroughly inspected, test run at the factory, and temperature.
  • Page 3: Removing From Storage

    REMOVING FROM STORAGE Electrical Disconnects As fans are removed from storage to be installed in their All fan motors should have disconnects located in close final location, they should be protected and maintained visual proximity to turn off electrical service. Service in a similar fashion, until the fan equipment goes into disconnects shall be locked-out when maintenance is operation.
  • Page 4: Lifting Information

    Lifting Information Roof Curb and Mounting Details CAUTION NOTE The cone is to be lifted by the cone lifting lugs, Steel, concrete or wood roof support is per structural separately and individually from the fan assembly. engineer and in accordance with load requirements and applicable building codes.
  • Page 5: Duct Installation - Bottom Inlet

    Duct Installation System Assembly Bottom Inlet Duct Connection NOTE The end of the duct (customer-supplied) is secured When installing each section, be certain to rig each between the roof curb’s top edge and the curb cap of section separately using the lifting lugs provided. either the Vektor-H or bypass air plenum.
  • Page 6: Kitchen Roof Mounting Installation

    Kitchen Roof Mounting Installation UL/cUL 762 installation are for restaurant applications. 1. The size of the duct must be equal to the inlet opening. 2. Secure the fan to curb at all four corners using a minimum eight anchor bolts, lag screws or other suitable fasteners.
  • Page 7: Plenum Drainage Piping And Trap Detail

    Plenum Drainage Piping / Trap for compatibility with the fan motor. In addition, the supply wiring must be properly fused and conform to Detail (By Others) local and national electrical codes. If the unit is supplied with a safety disconnect switch, ensure proper wiring to the fan motor.
  • Page 8: Variable Frequency Drive

    Vektor-H Applications with Variable Pre-Start-Up Checks Frequency Drive (VFD) Check all fasteners for tightness. For Vektor systems with single-point, three-phase Check radial gap, overlap and wheel alignment. The wheel should be aligned as shown. Although the wheel wiring per blower, the isolation damper actuator will be position is preset and the unit is test run at the factory, powered via a step-down transformer, which is wired to the fan disconnect, as shown in the wiring diagrams on...
  • Page 9: Maintenance

    For example, if the belt attaching the bearing to the bearing plate must be span is 64 inches, the checked for tightness. Greenheck Fan Corporation belt deflection should be recommends bearings to be relubricated quarterly at a one inch using moderate minimum.
  • Page 10: Bearing Relubication Schedule

    Recommended Bearing Lubrication Schedule Relubrication Schedule in Months* Fan Size 9 - 13 16 - 22 30 - 36 Bearing Bore (inches) ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ to 250 1000 1250 1500 2000 2500 3000 3500 0.75 4000 5000 Number of shots of...
  • Page 11: Parts List And Assembly

    Vektor-H and Vektor-HS Exhaust Fan Parts List and Assembly Each fan bears a manufacturer’s nameplate with model number and serial number embossed. This information in addition to the parts list shown, will assist the local Greenheck representative and the factory in providing service and replacement parts.