Coil Maintenance; Maintenance; Winterizing - Greenheck APEX-200 Installation, Operation & Maintenance Manual

Energy recovery ventilator
Table of Contents

Advertisement

Coil Maintenance

Filters upstream of the coil should be checked regularly. If the filters are dirty, they should be cleaned or
replaced. It is important that the coils stay clean to maintain desired airflow (refer to Filters in this section).
1. Coils must be clean to obtain maximum performance. Check once a year under normal operating
conditions and, if dirty, brush or vacuum clean. Soiled fins reduce the capacity of the coil, demand more
energy from the fan, and create an environment for odor and bacteria to grow and spread through the
conditioned zone. High pressure water (700 Psi or less) may be used to clean coils with fin thickness over
0.0095 inches thick. TEST THE SPRAY PRESSURE over a small corner of the coil to determine if the fins
will withstand the spray pressure.
For coils with fragile fins or high fin density, foaming chemical sprays and washes are available. Many coil
cleaners contain harsh chemicals, so they must be used with caution by qualified personnel only. Care
must be taken not to damage the coils, including fins, while cleaning.
CAUTION: Fin edges are sharp.
2. Drain pans in any air conditioning unit will have some moisture in them, therefore, algae and other
organisms will grow due to airborne spores and bacteria. Periodic cleaning is necessary to prevent this
build-up from plugging the drain and causing the
drain pan to overflow. Inspect twice a year to avoid
the possibility of overflow. Also, drain pans should be
kept clean to prevent the spread of disease. Cleaning
should be performed by qualified personnel.
Winterizing Coils
Coil freeze-up can be caused by such things as air stratification and
failure of outdoor air dampers and/or preheat coils. Routine draining of
water cooling coils for winter shutdown cannot be depended upon as
insurance against freeze-up. Severe coil damage may result. It is
recommended that all coils be drained as thoroughly as possible and then
treated in the following manner.
Fill each coil independently with an antifreeze solution using a small
circulating pump and again thoroughly drain. Check freezing point of
antifreeze before proceeding to next coil. Due to a small amount of water
always remaining in each coil, there will be diluting effect. The small
amount of antifreeze solution remaining in the coil must always be
concentrated enough to prevent freeze-up.
NOTE: Carefully read instructions for mixing antifreeze solution used.
Some products will have a higher freezing point in their natural state than
when mixed with water.
Routine Maintenance
21
SAFETY CAUTION!
Biological hazard. May cause disease. Cleaning
should be performed by qualified personnel.
®

Advertisement

Table of Contents
loading

Table of Contents