Overvoltage Stall Level (fast)
Overvoltage Stall Level (fast)
Program
Protection Settings
This parameter sets the upper DC bus voltage threshold that, once exceeded,
will cause an Overvoltage Stall. An Overvoltage Stall increases the output
frequency of the ASD during deceleration for a specified time in an attempt to
prevent an Overvoltage Trip.
If the overvoltage condition persists for over 250 µS, an Overvoltage Trip will
be incurred.
Note: This feature may increase deceleration times.
Panel Acceleration/Deceleration Select
Program
Panel Control
This parameter is used to select 1 of 4 accel/decel profiles that may be
configured and run. Each accel/decel profile is comprised of 3 user settings:
Acceleration, Deceleration, and Pattern.
Settings:
Acceleration/Deceleration #1
Acceleration/Deceleration #2
Acceleration/Deceleration #3
Acceleration/Deceleration #4
Panel Direction
Program
Panel Control
This parameter sets the motor direction while operating from the keypad.
Panel Operation Inhibit Selection
Program
Utilities
Display Attributes
Selection
This parameter disables the selected keypad function.
Settings:
Allow All Keys
Allow Emergency Off Only
Panel PID Control
Program
Panel Control
Enables/Disables PID control while operating from the keypad.
Panel Reset Selection
Program
Panel Control
Enables/Disables the ability to reset the system from the keypad.
W7 ASD Installation and Operation Manual
Overvoltage Stall Level (fast)
Panel Acceleration/Deceleration Select
Panel Direction
Panel Operation Inhibit
Panel PID Control
Panel Reset Selection
Panel Reset Selection
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 50.00
Maximum — 250.0
Units — %
Parameter Type — Selection List
Factory Default — Acceleration/
Deceleration #1
Changeable During Run — Yes
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — Yes
Parameter Type — Selection List
Factory Default — Allow All Keys
Changeable During Run — Yes
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
95