Wireless Remote Control - Carrier RAV-SP180UT-UL Installation Manual

Air conditioner (split type); 4-way air discharge cassette type
Hide thumbs Also See for RAV-SP180UT-UL:
Table of Contents

Advertisement

4-way Air Discharge Cassette Type

Wireless remote control

1
Procedure
Turn on the power of the air conditioner.
When power is turned on for the first time after
installation, it takes approx. 5 minutes until the remote
control becomes available. In the case of subsequent
power-on, it takes approx. 1 minute until the remote
control becomes available. Execute a test run after the
predetermined time has passed.
2
Procedure
Push "ON/OFF" button on the remote control, select
[COOL] or [HEAT] with "MODE" button, and then select
[HIGH] with "FAN" button.
3
Procedure
Cooling test run
Set the temperature to 64 °F
(18°C) with the temp. setup
buttons.
4
Procedure
Cooling test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 66 °F (19°C)
with the temp. setup buttons.
5
Procedure
Cooling test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 64 °F (18°C)
with the temp. setup buttons.
6
Procedure
4
5
Repeat procedures
Indicators "Operation" (green), "Timer" (green), and
"Ready" (orange) in the wireless receiver section flash
in approx. 10 seconds, and the air conditioner starts
operation. If any of these indicators does not flash,
2
5
repeat procedures
to
.
7
Procedure
Upon completion of the test run, push "ON/OFF" button
to stop operation.
<Overview of test run operations using the
wireless remote control>
▼ Cooling test run:
ON/OFF → 64 °F (18 °C) → 66 °F (19 °C) → 64 °F (18
°C) → 66 °F (19 °C) → 64 °F (18 °C) → 66 °F (19 °C)
→ 64 °F (18 °C) → (test run) → ON/OFF
Heating test run
Set the temperature to 86 °F
(30°C) with the temp. setup
buttons.
Heating test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 84 °F (29°C)
with the temp. setup buttons.
Heating test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 86 °F (30°C)
with the temp. setup buttons.
4
5
.
▼ Heating test run:
ON/OFF → 86 °F (30 °C) → 84 °F (29 °C) → 86 °F (30
°C) → 84 °F (29 °C) → 86 °F (30 °C) → 84 °F (29 °C)
→ 86 °F (30 °C) → (test run) → ON/OFF
Always select
[HIGH] fan
speed.
2
2
– 32 –
Installation Manual
3, 4,
5, 6
2,7
EN
32-EN

Advertisement

Table of Contents
loading

Table of Contents