CLEARANCES
CLEARANCES
TO COMBUSTIBLES
COMBUSTIBLE
Floor ......................................
Right Side ..............................
Left Side ................................
Back ......................................
CLEARANCE
0 Inches (0 cm)
0 Inches (0 cm)
0 Inches (0 cm)
0 Inches (0 cln)
Front ......................................
16 Inches (41 cm)
Ceiling ....................................
36 Inches (91 cm)
Draperies ................................
4 Inches (10 cm)
Vent ........................................
2.5 Inches (6.35 cm)
If the heater is installed
directly
on carpeting,
tile or other com-
bustible
material
other than
wood flooring,
the heater shall
be installed
on a metal or wood
panel extending
the full width
and depth of the heater.
VENT
CAP CLEARANCES
FIG.
1
OUTSIDE
LOCATION
FOR VENT OUTLET
TERMINAL
A
Clearance above grade, veranda, porch, deck or balcony
(* 12 inches [30cm] minilnuln)
B
Clearance to window or door that may be opened
(*6 inches [ 15 cm] minimum)
C
Clearance to permanently closed window (minilnum 12
inches [30 cm] recommended to prevent condensation
on window)
D
Vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 2 feet [60 cm]
fiom the center-line of the terminal (18 inches [46 cm]
minimum)
E
Clearance to unventilated soffit (12 inches [30 cm]
minimum)
F
Clearance to outside corner(12 inches [30 cm]
minimum)
G
Clearance to inside corner (24 inches [60 cm]
minimum)
H
*Not to be installed above a meter / regulator assembly
within 3 feet [90 cm] horizontally from the center-line
o f the regulator
I
Clearance to selaTiceregulator vent outlet (*6 feet [ 1.8 m]
minimum)
Page 4
J
Clearance to non-mechanical air supply inlet to building
or the combustion air inlet to any other appliance (* 12
inches [30 cm] minimum)
K
Clearance to a mechanical air supply inlet (*6 feet
[1.8 m] minimum)
L
_" Clearance above paved side-walk or a paved driveway
located on public property (*7 feet [2.1 m] minimum)
M
Clearance under a veranda, porch, deck or balcony
(* 12 inches [30 cm] minilnuln_)
"? A vent shall not terminate directly above a sidewalk or
paved driveway which is located between two single
family dwellings and selaes both dwellings*.
Only permitted if veranda, porch, deck or batcony is
tully open on a minimum of 2 sides beneath the floor.
* As specified in CGA B 149 installation codes, NOTE:
local codes or regulations may require different
clearances.