WINTERIZATION
_)
[]NIT
AND PROPERTY
DAMAGE
HAZARD
Failure
to follow
this caution may result in unit component
or
property
damage.
If the furnace
is installed
in an unconditioned
space where the
ambient
temperatures
may be 32 ° F (0 ° C) or lower, freeze
protection
measures
must be taken to prevent
minor property
or product
damage.
Since
the furnace
uses a condensing
heat exchanger,
some water
will accumulate
in the unit as a result of the heat transfer
process.
Therefore,
once it has been
operated,
it cannot
be turned
off and
left off for an extended
period
of time when
temperatures
will
reach
32°F
(0°C)
or
lower
unless
winterized.
Follow
these
procedures
to winterize
your furnace:
1. Obtain
propylene
glycol
(RV/swimming
pool
antifreeze
or
equivalent).
UNIT
COMPONENT
DAMAGE
HAZARD
Failure
to follow
this caution
may
result
in damage
to the
furnace
and other property
damage.
Do not use ethylene
glycol
(Prestone
II antifreeze
coolant
or
equivalent).
Failure of plastic components
may occur.
2. Turn off electrical
supply
to your furnace.
3. Remove
main furnace
door.
4. Remove
upper inducer
housing
drain connection
cap.
See
Fig. 38.
5. Connect
field-supplied
1/2-in.
(13 mm)
ID tube to upper
inducer
housing
drain connection.
6. Insert field-supplied
funnel into tube.
7. Pour
1 quart
of
antifreeze
into
funnel/tube.
Antifreeze
should
run through
inducer
housing,
overfill
condensate
trap, and flow into open field drain.
See Fig. 39.
8. Remove
funnel
and tube from
inducer
housing
and replace
drain connection
cap and clamp.
9. Replace
main furnace
door.
10. Propylene
glycol need not be removed
before restarting
fur-
nace.
13
Fig. 38 - Drain
Connection
Cap
Fig. 39 - Antifreeze
into Funnel
/ 1hbe