Coleman DVF32TMHST SERIES Installation Instructions Manual page 6

See-thru direct vent gas fireplace
Table of Contents

Advertisement

VENT INSTALLATION INSTRUCTIONS
1. Install pipe to fireplace collar adapter located on back
of unit at a 45 deg. Angle. Connect our starting pipe
to a 45 deg. Starting section by sliding it over the
collar adapter on the fireplace. Twist-lock for proper
installation check to insure proper connection (see
figure 7).
Figure 7
VENT INSTALLATION
2. Once the elbow is properly fastened to the fireplace
adapter, continue to install the remainder of the pipe
for the desired installation.
3. Install every section of the pipe making sure that all
joints are properly twist-locked.
4. After steps 1, 2 and 3 are completed, install the vent
termination. Depending on location of termination,
you may use a vertical or horizontal termination.
5. Depending on the wall thickness, allow one inch to
protrude from internal wall as shown in figure 8.
Figure 8
6. An optional siding standoff may be installed between
the vent cap exterior wall. Secure horizontal top to
standoff and then secure the complete assembly to
wall (see figure 8). The vent termination must be
removable for service pipe inspection.
7. For vertical installation, use vertical termination.
The vent system serves as the "chimney" as well as the
combustion air supply (air intake). The horizontal run must
have a rise of ¼" (6 mm) for every 1 foot (305 mm) of
horizontal run towards the termination. Never allow the vent
to run downward. The maximum horizontal run depends on
the vertical rise from fireplace adapter collar to the vent
termination (see table below).
VERTICAL
ft
0
1
2
3
4
5
6
7
8
WARNING: Vent pipe air space clearances to
combustibles are 1" on all sides except on the horizontal
sections, which require 2" clearances from the top of the
pipe. Where the termination cap penetrates a combustible
wall, 1" air space clearance is required.
When installing length of pipe over 3 ft. (914 mm), support
the pipe every 3 ft. (914 mm) using metal straps. Vertical to
horizontal pipe must be kept at a one foot (305 mm) to 4 ft.
(1219 mm) ratio with a maximum run of no more than 20 ft.
If an offset is necessary in the attic to avoid obstruction, it is
important to support the vent pipe every 3 ft. (914 mm), to
avoid excessive stress on the elbows and possible separation
see figure 9).
Figure 9
-5 -
HORIZONTAL
mm
ft
to
1'
305
to
4
610
to
8
914
to
12
1219
to
16
1524
to
15
1829
to
14
2134
to
13
2438
to
12
OFFSET ELBOW
For more information, visit www.desatech.com
mm
305
1219
2438
3658
4877
4572
4267
3962
3658

Advertisement

Table of Contents
loading

Table of Contents