10 FOOT RULE

All flue gas outlet chimney terminations must
extend a minimum of 3 feet in height above
highest point where it passes through roof and
must be at least 2 feet above highest point of
the roof that is within a horizontal distance of
10 feet (see Figure 19).
10'
2' Min.
Figure 19 - 10 Foot Rule
EFFECTIVE HEIGHT
OF TERMINATION CAP
14.5 FT.
MINIMUM
HEIGHT
1
VenTing inSTallaTion
Level of
Flue Gas
Outlet
10'
3' Min.
2' Min.
EFFECTIVE HEIGHT
OF TERMINATION CAP
14.5 FT.
MINIMUM
HEIGHT
UP TO
6FT. MAX.
Figure 20 - Typical Residential Installations
www.desatech.com
Continued
FINISHING FIREPLACE
Combustible materials, such as wallboard,
gypsum board, sheet rock, drywall, plywood,
etc., may make direct contact with sides and
top around fireplace face. It is important that
combustible materials do not overlap face
itself. Brick, glass, tile or other noncombustible
materials may overlap front face provided
they do not obstruct essential openings such
as louvered slots. When overlapping with
a noncombustible facing material, use only
noncombustible mortar or adhesive.
3' Min.
EFFECTIVE HEIGHT
OF TERMINATION CAP
30E-8DM
EFFECTIVE HEIGHT
OF TERMINATION CAP
MAX. HEIGHT
50 FT.
(ANY SYSTEM)
UP TO
6FT. MAX.
MIN. HEIGHT
OF 22 FT. (WITH
2 ELBOW SETS)
MAX. HEIGHT OF
50 FT.
30E-8DM
115385-01B