Operating test, address selector, fault code,
guide for the owner and accessories

Operating test

• Perform the operating test after the units have been installed in
position and the gas leak test has been completed.
• Check all electrical connections (instructions and wiring diagram).
• Insert the batteries into the remote control and leave it OFF.
• Energise the system, turning the power supply ON.
• Press the
and
buttons of the infrared remote control and
hold them pressed for more than 5 seconds.
The display will be cleared, the time segments will display the icon
(Src = service test).
• After test has been completed, press
menu.
Note:
When 30 seconds have elapsed and no buttons have been
pressed, the remote control will automatically exit the test menu
and resume its normal operation.

Address selector

If you are installing two indoor units in the same room and you want
them to operate in independent mode, it is necessary to assign
each unit its own address so that each unit can operate via its own
remote control.
For configuration, proceed as follows:
Configuration (of the unit)
• Press the
and
buttons of the infrared remote control and
hold them pressed for more than 5 seconds.
• The display will be cleared, the time segments will display the first
configuration item (rAdr = remote address) and the temperature
segments will display the default value of this configuration item
(Ab = control of both indoor units).
• Press either the
or
button to change the default value (Ab) to
the new value (A) or (b).
• Press
button to transmit the new configuration to the unit.
• Press
button to leave the configuration menu.
Configuration (of the remote controller)
• Press the
and
buttons of the infrared remote control and
hold them pressed for more than 5 seconds.
• The display will be cleared, the temperature segments will display
the first configuration item (CH = remote address) and the time
segments will display the default value of this configuration item
(Ab = control of both indoor units).
• Press either the
or
button to change the default value (Ab) to
the new value (A) or (b).
• Press
button to transmit the new configuration to the unit.
• Press
button to leave the configuration menu.
Note:
When 30 seconds have elapsed and no buttons have been
pressed, the remote control will automatically exit the configuration
menu and the procedure has to be restarted.
Table VII: Accessories
Description
Condensate discharge pump 230V ~ 50Hz
Cable cover kit
button to leave the test
Part number
42VKG9002
42VKG9003

Fault code

Once a failure occurs with the indoor unit in operation, the green
unit LED flashes at intervals of 0.5 seconds.
The fault code is deduced from the number of times the green LED
flashes, blocking unit operation.
Between one flash cycle and the next one, a pause of 5 seconds
elapses.
Table VI: Fault code
Code
Description
3
Room air sensor fault
4
Indoor unit coil sensor fault
6
Filter dirty
7
Outdoor unit failure
10
EEPROM corrupt
11
Unit address incomplete
12
Address / zone incomplete
13
Gas flow distributor corrupt

Guide for the owner

When installation and tests are completed explain the Operation
and Maintenance Manual to the owner, with particular attention to
the main operating modes of the air conditioner, such as:
• Turning the unit on and off.
• Functions of the remote control.
• Removal and cleaning of the air filters.
Leave the two installation manuals for the indoor and outdoor units
with the owner for future use during maintenance operations or for
any other needs.