UNIT
SIZE
024
030, 036
042, 048
060
* For tube sets greater than 50 ft, consult Residential Split System Application Guideline and Service Manual.
CERTIFICATION APPLIES ONLY
WHEN THE COMPLETE SYSTEM
IS LISTED WITH ARI.
RECOMMENDED TUBE DIAMETERS
Liquid Tube Diameter (In.)
0 to 50 Ft
Tube Length
Long-Line Applications*
3/8
CHECK-FLO-RATER® PISTON
UNIT SIZE–SERIES
024-A
030-A
036-A
042-A
048-A
060-A
* Piston listed is for any approved non-capillary tube coil combination. Piston is shipped
with outdoor unit and must be installed in an approved indoor coil.
CHARGING SUBCOOLING (TXV-TYPE EXPANSION DEVICE*)
UNIT SIZE–SERIES
024-A
030-A
036-A
042-A
048-A
060-A
* Must be a Puron® approved hard shutoff TXV.
®
As an ENERGY STAR
partner, Bryant Heating &
Cooling Systems has
determined that this prod-
uct meets the ENERGY
®
STAR
guidelines for
energy efficiency.
0 to 50 Ft
Tube Length
5/8
3/4
3/8
7/8
1-1/8
PISTON*
IDENTIFICATION NO.
61
63
70
76
76
90
REQUIRED SUBCOOLING (°F)
10
15
12
15
15
15
REGISTERED QUALITY SYSTEM
—3—
Vapor Tube Diameter (In.)
Long-Line Applications*
(Maximum Diameter)
3/4
7/8
1-1/8
1-1/8