2000 Series | Program Entry Guide | 11.0
Table 5: continued
Display
Selection
B
Extended Delay, All
Bosch Security Systems | 7/05 | 35114F
Point Codes
Description
When control panel is All On (armed) short or open starts Extended Delay if no
Trouble option. Section 11.3 Digit 3, Point Options. You must fault the Extended
Delay point first. If a Non-Extended Delay point is faulted first, extended delay is
not used.
Faulting an Extended Delay point when the system is in exit delay extends exit
delay to the value programmed in the Extended Delay prompt. Refer to the
Extended Delay prompt in Section 6.0 Open/Close for a detailed explanation of
the Extended Delay feature.
Extended Delay points must be normal (not faulted) or bypassed before the
system can be All armed.
Note:
If you bypass an Extended Delay Point the system switches to the Extended Delay.
The system makes the switch even if the point is not faulted when you bypass it.
Extended Delay points that are bypassed and restored during exit delay are
automatically unbypassed and returned to the system.
If an alarm occurs on these points within 2 minutes of a closing (exit time expired,
Excursion/Exit included), the system sends a RECENT CLOSING message with
the Alarm Report.
If these points are faulted at the end of exit delay, the system waits a period equal
to entry delay before sending an Alarm Report. If the system is not turned off, it
sends an EXIT ERROR message with the Alarm Report.
Missing Extended Delay points generate an alarm response when on, a trouble
response when off.
RF tamper for an Extended Delay point generates an alarm response when on, a
trouble response when off.