Wiring - Main Power; Wiring - Low Voltage Wiring; Figure 15 Component Location; Table 3 Operating Voltage Range - Bard Q24A1 Installationair conditioner Instructions Manual

Q-tec series packaged air conditioner
Table of Contents

Advertisement

WIRING – MAIN POWER
Refer to the unit rating plate and/or Table 2 for wire
sizing information and maximum fuse or "HACR Type"
circuit breaker size. Each unit is marked with a
"Minimum Circuit Ampacity". This means that the
field wiring used must be sized to carry that amount of
current. Depending on the installed KW of electric
heat, there may be two field power circuits required. If
this is the case, the unit serial plate will so indicate. All
models are suitable only for connection with copper
wire. Each unit and/or wiring diagram will be marked
"Use Copper Conductors Only". These instructions
MUST BE adhered to. Refer to the National Electrical
Code (NEC) for complete current carrying capacity data
on the various insulation grades of wiring material. All
wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C
copper) for all models, including the most commonly
used heater sizes. Also shown are the number of field
power circuits required for the various models with
heaters.
The unit rating plate lists a "Maximum Time Delay
Relay Fuse" or "HACR Type" circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection, and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.
FIGURE 15
COMPONENT LOCATION
ELECTRIC
HEATERS
UNIT
MOUNTED
THERMOSTAT
LOCATION
DEHUMIDIFICATION
CONTROL
(OPTIONAL)
Manual 2100-522B
Page
20 of 38
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.
See "Start Up" section for information on three phase
scroll compressor start-ups.
The field wiring connections are located behind the top
and hinged panel in the circuit breaker panel. See
Figure 15.
WIRING – LOW VOLTAGE WIRING
230/208V, 1 PHASE AND 3 PHASE EQUIPMENT
DUAL PRIMARY VOLTAGE TRANSFORMERS.
All Equipment leaves the factory wired on 240V tap.
For 208V operation, reconnect from 240V to 208V tap.
The acceptable operating voltage range for the 240 and
208V taps are as noted in Table 3.
NOTE: The voltage should be measured at the field
The standard Climate Control Option X is a remote
thermostat connection terminal block. See Figure 17 for
wiring diagram. Compatible thermostats are listed in
Table 4.
The Climate Control Option A is an electronic, non-
SIDE FIELD WIRE
programmable manual or auto changeover thermostat.
ENTRANCE
The subbase of the thermostat is factory wired to the
front panel of the unit. See Figure 18 for wiring
diagram. Compatible for use with Bard CS2000A*
REMOTE
Controller and Energy Recovery Ventilator.
THERMOSTAT
TERMINAL
The Climate Control Option D is an electronic,
BLOCK
programmable thermostat. The subbase of the
INDOOR
thermostat is factory wired to the front panel of the unit.
BLOWER
See Figure 19 for wiring diagram. Compatible for use
with Energy Recovery Ventilator or Economizer.
The Climate Control Option H is an electronic,
programmable thermostat and a CO
subbase of the thermostat and CO
CIRCUIT
wired to the front panel of the unit. See Figure 20 for
BREAKER PANEL
& CONTROLS
wiring diagram.
NOTE: On option X or A the CS2000A* (or other field
LOWER
CONTROL
PANEL
NOTE: Thermostats are shipped in the bottom of the
TABLE 3
OPERATING VOLTAGE RANGE
T
A
P
R
2
4
0
V
2
5
2
0
8
V
2
2
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
2
provided means to control ventilation) must be
used if any of the motorized ventilation options
are installed.
unit and must be mounted to the factory
mounted subbase at time of installation.
A
N
G
E
3
2
1
6
0
1
8
7
controller. The
2
controller are factory

Advertisement

Table of Contents
loading

Table of Contents