Figure 2 Slab Mounting At Ground Level; Figure 3 Airflow And Service Access Clearances - Bard PA13241-A Installation Instructions Manual

Single package air conditioners
Table of Contents

Advertisement

1 inch clearance
between duct and
any combustible
material if distance
between outside
Supply Duct
wall and unit is less
than 3 feet (needed
on electric heat
units only).
Return Duct
Manual 2100-467D
Page
10 of 25
FIGURE 2
SLAB MOUNTING AT GROUND LEVEL
The distance between
outside wall and unit
varies with installation
requirements.
Building
FIGURE 3
AIRFLOW AND SERVICE ACCESS CLEARANCES
Heater Package
Access
Heater Package
Blower
and
Blower Motor
Blower Service
Access
Air Outlet
Nearest Structure
Control Panel
36" min.
Access
Control Panel
Comp-
ressor
24" min.
Air Inlet
Nearest Structure
Side
View
Package Unit
Mounting Slab
1/4 inch per foot
slope away
from building
Ground Level
Top
Compressor
View
Access
24" min.
Condenser fan
and motor access
from top.
Leave 60" min.
above fan.
MIS-2143