Shipping Damage; General; Table 2 Electrical Specifications - Bard W12A2-A Installation Instructions Manual

Wall mounted package air conditioners
Table of Contents

Advertisement

Rated Volts
Models
and
Phase
W12A2-A00
A03
230/208-1
A05
W12A1-K00
115-1
K02
j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
 Based on 75°C copper wire. All wiring must conform to NEC and all local codes.
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National
Electrical Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be
derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3
conductors are in a raceway.

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked
for external signs of shipping damage. If damage is
found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier's agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
air ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.
Manual 2100-509E
Page
6 of 17
TABLE 2
ELECTRICAL HEAT SPECIFICATIONS
SINGLE CIRCUIT
No. Field
Minimum
Power
Circuit
Circuits
Ampacity
1
9
1
20
1
28
1
20
1
29
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly "Starting
Procedure" and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation
is made. See Page 3 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss/gain calculation made according to methods
of Air Conditioning Contractors of America (ACCA).
The air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
j
Maximum
External Fuse
Field Power
or Circuit
Wire Size
Breaker
15
14
20
12
30
10
30
10
30
10
Ground
Wire Size
14
12
10
10
10