First Ignition; Adjust The C.h. Ignition Delay; Regulating The Maximum C.h. Power & Soft Ignition - Ariston E-Combi 24 Installation And Servicing Instructions

Condensing wall hung combination boiler; condensing wall hung o.h. boiler
Hide thumbs Also See for E-Combi 24:
Table of Contents

Advertisement

commissioning
irst ignition
1. Make sure that:
- The gas valve is closed;
- The electrical connection has been properly carried out. Make sure
that the green/yellow earthing wire is connected to an effi cient
earthing system;
- Use a screwdriver to lift the cap on the automatic air relief valve;
- Switch on the boiler (by pressing the ON/OFF button), the green
led 3 will illuminate indicating that the boiler is ready to operate.
Turn the CH button 5 between min. and max position. The pump
will start and the burner will attempt to light, after 7 seconds
the boiler will lock out because there is no gas; the red Led 8
illuminates.
50°
40°
on/off
-
Bleed the air from the radiators;
-
The fl ue should be suitable and free from any obstructions;
2. Open the gas cock and check the connection seals, including the
boiler connection joints, making sure that the meter does not
detect any passage of gas. Eliminate any leaks.
3. Unlock the boiler by pushing the reset button. The burner will
light, if the fi rst start fails repeat the operation until the burner
lights.
Setting
Regulating the central heating ignition delay
Adjust the central heating ignition delay
1. Push ON/OFF button for 10 seconds, the red reset led
blinks.
2. Pressing the RESET button, the green led blinks.
3. Adjusting with the CH knob (Temporisation 0, 1, 2, 3, 4, 5, 6
minutes see table).
Green Leds
Temperature indicator
40
50
60
70
80
90 *
* This LED is red
30
60°
70°
80°
90°
I
O
● = no led lit
TAC
● = lit
0 min
1 min
2 min
3 min
4 min
5 min
6 min
50°
40°
2
MIN
5
MAX
Adjust maximum C.H. power
Regulating the maximum central heating power & soft
ignition
Regulate the maximum central heating power (between minimum
and maximum) to adjust the central heating power and the soft
ignition :
Adjust the setting on the front panel
1. Push ON/OFF button for 10 seconds, the red reset led blinks.
2. Adjusting with the CH knob the maximum CH power between 0
and 99 % (see table).
3. Combi only adjusting with the DHW knob the soft ignition
between 0 to 99% (see table). The percentage level is visualized
by the green led.
4. To store the new values of settings, it is enough to push ON/OFF
button.
IMPORTANT!!
For E-SYSTEM boiler
To adjust the Soft Ignition it is necessary remove the cover using a
screwdriver, see fi g. a, and alter the soft ignition by adjusting the
potentiometer, see fi g. b.
fi g. a
on/off
Green Leds
Temperature indicator
40
50
60
70
80
90 *
* This LED is red
60°
70°
80°
90°
8
MIN
MAX
Adjust Soft Ignition
fi g. b
on/off
Max adjustable
● = no led lit
power and soft
● = lit
ignition
0 to 39 %
40 to 49 %
50 to 59 %
60 to 69 %
70 to 79 %
80 to 89 %
90 to 99 %
6