Specification - LG LMCN125HV Service Manual

Multi air conditioner
Hide thumbs Also See for LMCN125HV:
Table of Contents

Advertisement

1. Specification

Indoor unit type
Model
Decoration Panel Name
Power Supply
Capacity(*)
Current
Running Current
Fan
Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate
(H / M / L)
External Static Pressure
Capacitor
Drive
Coil
Row x Column x FPI
Dimensions
Body
(W x H x D)
Decorative Panel
Net Weight
Body
Decorative Panel
Air Filter
Sound Level (H / M / L)
Piping
Liquid
Connections
Gas
Drain(OD/ID)
Dehumidification Rate
Safety Devices
Temperature Sensor
Referigerant
Referigerant Control
Transmission Interunit Cable
Note:
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F)
- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F)
Heating: - Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB
- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB
Piping Length - Interconnecting Piping Length 7.5m(24.6 ft.)
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
4. For more Capacity(*),refer to the combination table
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
AMNW12GTRA0[LMCN125HV]
PT-UQC
Ø / V / Hz
1/ 208~230/ 60
Btu/h class
12,000
A
0.25
BLDC
Turbo Fan
43 x 1
CMM
9.5/ 8/ 7
CFM
335/282/247
mmAq
µF / Vac
Direct Drive
2R x 8C x 18
mm(inch)
570 x 214 x 570 ( 22 7/16 x 8 7/16 x 22 7/16) 570 x 256 x 570 ( 22 7/16 x 10 x 22 7/16)
mm(inch)
700 x 30 x 700 (27 6/19 x 1 3/16 x 27 6/19) 700 x 30 x 700 (27 6/19 x 1 3/16 x 27 6/19)
kg (lbs)
14 (30.9)
kg (lbs)
3 (6.6)
Long life filter
dB(A)+3
38/ 35/ 32
mm (inch)
6.35 (1/4)
mm (inch)
9.52 (3/8)
mm(inch)
32 / 25(1.26/0.984)
l/h
Fuse, thermal protector for fan motor Fuse, thermal protector for fan motor
Thermistor
R410A
EEV(in Outdoor unit)
No. x AWG
4X18(Including Earth)
- 2 -
Ceilling Cassette - 4way
AMNW18GTQA0[LMCN185HV]
1/ 208~230/ 60
-
-
2R x 10C x 18
Long life filter
32 / 25(1.26/0.984)
2
EEV(in Outdoor unit)
4X18(Including Earth)
Conversion Formula
kW = Btu/h class X 0.0002931
cfm = CMM x 35.3
PT-UQC
18,000
0.25
BLDC
Turbo Fan
43 x 1
13/ 12/ 11
459/424/388
-
-
Direct Drive
15 (33.1)
3 (6.6)
38/ 37/ 34
6.35 (1/4)
12.7 (1/2)
2
Thermistor
R410A
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmcn185hvAmnw12gtra0Amnw18gtqa0