Table 8 P9500 Electrical specifications - single phase current
Item
Power requirements, system
operating
Power consumption, system
in standby
16
Installation requirements
Unit
AC, single phase 2 pole +
ground
Drive Rack (384 HDD)
Maximum
Controller chassis power
supply
Drive chassis power supply
Control chassis
Drive chassis
Rack with one control
chassis and two drive
chassis
Rack with three drive chassis
Single module (3 rack
system)
Dual module (6 rack system)
Specification
200 V to 240 V, +6% -8% 50 Hz ±3 Hz, 60 Hz ± 2 Hz
5.1KVA (2.5" SAS)
31.4 KVA
Input Current
Steady Current
Leakage Current
Inrush current
Input Current
Steady Current
Leakage Current
Inrush current
0.79 KVA
1.34 KVA
3.47 KVA
4.02 KVA
1 1.51 KVA
23.02 KVA
7.18 A
3.59 A
0.28 mA
1st (0-p) 20 A
2nd (0-p) 15A
1st (0-p) Time (-25%: 80 ms
6.52 A
3.26A
0.28 mA
1st (0-p) 20 A
2nd (0-p) 15A
1st (0-p) Time (-25%: 80 ms