W I R I N G
2
6 Wires, 16 AWG from operator in dedicated water tight
conduit.
REV A
Caution:
Do Not use wire less than 16 gauge
up to 200 Ft.
SINGLE OR MASTER ONLY
MOTOR
BRAKE
LIMITS
1
2
3
4
5
6
Removable Terminal Connectors
1
2
3
4
5
6
Master
Removable
Terminal
Wire
Connector
Caution:
Make sure BARE WIRE
makes good contact inside removable
terminal connectors.
DO NOT
insulation interfere with connection.
O P E R A T O R S
LAKE FOREST, CALIFORNIA
DO NOT run AC lines in same conduit!
Operator 1
(Master)
SECOND ONLY
MOTOR
BRAKE
LIMITS
7
8
9
10
11
12
7
8
9 10 11 12
Second
Supplied
let wire
17
M A S T E R
®
www.eliteaccess.com
Operator 2
(Second)
13
14
15
16
17
REV A
SINGLE OR MASTER ONLY
SECOND ONLY
MOTOR
BRAKE
LIMITS
MOTOR
BRAKE
1
2
3
4
5
6
7
8
9
10
Supplied Conduit
Important:
Install the Conduit (supplied) to secure
the Master Operator to the Control Board
Box.
Install a dedicated water tight conduit
for the Second Operator. DO NOT run AC
wire in same conduit as 6 wires!
Water
Tight
Conduit
More than 20 ft run, you MUST use
(Not
Shielded Wire for the blue and green
Supplied)
lines. Shield must be grounded .
/
S E C O N D
Water Tight
J-Box Kit
Elite # K55-09853
18
19
20
21
22
23
24
25
®
LAKE FOREST, CALIFORNIA
www.eliteaccess.com
LIMITS
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
26
27