Download Print this page

Installation - KUSSMAUL 091-141 Instruction Manual

Battery protector

Advertisement

INSTALLATION

WIRING:
Figure 2 illustrates the wiring of the Load Manager P. Wire the unit using the
wire gauges shown in figure 2.
SIZE FUSE
FOR 25% HIGHER
THAN ACTUAL
LOAD
FROM
12 or 24
VOLT
BATTERY
INSTALLATION WIRING, LOAD MANAGER P
ALIGNMENT:
Refer to Figure 3 for all component locations and measurement points.
12VDC Operation:
R102 is normally set maximum counter-clockwise for an 11.0 volt threshold.
R102 can be adjusted in a clockwise direction to obtain a higher threshold
voltage. Maximum clockwise is 12.85 volts.
24VDC Operation:
R102 is normally set approximately 70% of full counter-clockwise for a 22.0 volt
threshold. R102 can be adjusted in a clockwise direction to obtain a higher
threshold voltage. Maximum clockwise is 24.75 volts, maximum counter-
clockwise is 21.25VDC.
R103 is normally set maximum counter-clockwise for a 1-hour time threshold.
R103 can be adjusted in a clockwise direction to obtain a longer time threshold.
Maximum clockwise is 2 hours.
#12 AWG, RED
1
2
#20 AWG, RED
#20 AWG, BLACK
FROM
STARTER
SWITCH
(0PTIONAL)
Figure 2
#12 AWG, ORANGE
NO
C
4
3
#20 AWG,
YELLOW
RADIO &
COMPUTER
+
LOADS
-

Advertisement

loading

This manual is also suitable for:

Load manager p091-141-24