Grounding The Chassis - Cisco UC540W-BRI-K9 - Uc System With 2BRI 1VIC Exp Quick Start Manual

Unified communications 500 series
Hide thumbs Also See for UC540W-BRI-K9 - Uc System With 2BRI 1VIC Exp:
Table of Contents

Advertisement

Attach the power supply bracket to the wall.
S
3
TEP
The following illustration shows the wall-mount bracket for the
power supply and the mounting-screw holes on the back of the
bracket.
Mounting
screws (2)
a.
Attach the bracket to the wall by using the mounting hardware
specified in
b. Orient the front and back of the power supply vertically.
c.
Position the end nearest the power cable at the top.

Grounding the Chassis

The UC 540 chassis must be reliably grounded with a supplementary
ground wire to comply with the relevant product safety standards. This
supplementary ground is in addition to the ground connection made by the
power cord.
For the supplementary ground connection, use size 14 AWG (2 mm) or
larger copper wire and an appropriate user-supplied ring terminal with an
inner diameter of 1/4 inch (5 to 7 mm).
The UC 540 is not NEBS-compliant.
N
OTE
To connect the chassis to a reliable earth ground:
Strip one end of the ground wire to the length required for the
S
1
TEP
ground lug or terminal.
For the ground lug, strip approximately 0.75 in. (20 mm).
For the user-provided ring terminal, as required.
Cisco Unified Communications 500 Series Model UC 540 Quick Start Guide
Step
1.
11