Desa BG30N Safety Information And Installation Manual page 14

Unvented (vent-free) blue flame gas garage heater
Table of Contents

Advertisement

2. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve
located on or near gas meter for natural gas
or using compressed air.
3. Check all joints from gas meter for natural gas
(see Figure 17) or propane/LP supply tank for
propane/LP gas, to equipment shutoff valve
(see Figure 18). Apply a noncorrosive leak
detection fluid to all joints. Bubbles forming
show a leak.
4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 16,
page 13).
2. For natural gas open main gas valve located
on or near gas meter. For propane/LP gas open
propane/LP supply tank valve.
3. Make sure control knob of heater is in the OFF
position.
4. Check all joints from equipment shutoff valve
to thermostat gas valve (see Figure 17 or 18).
Apply a noncorrosive leak detection fluid to
all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operating Heater, starting
on page 15). Check all other internal joints for
leaks.
7. Turn off heater (see To Turn Off Gas to Appli-
ance, page 16 or 17, depending on your model
heater).
8. Replace front panel.
14
Gas
Meter
Figure 17 - Checking Gas Joints for
Propane/LP
Supply Tank
Figure 18 - Checking Gas Joints for
www.desatech.com
Thermostat Gas Valve
Equipment Shutoff Valve
Natural Gas
Thermostat Gas Valve
Equipment Shutoff Valve
Propane/LP Gas
114683-01B

Advertisement

Table of Contents
loading

Table of Contents