VENTILATION

OPERATION

Never use heater without properly installed vent pipe and
regulator. You must vent heater to the outdoors. This assures
proper combustion and avoids air contamination in the room.
A standard 4 inch (10.16 cm) draft regulator is required only if total vertical and
horizontal length of the vent pipe exceeds 20 feet (6.1 meters). Regulator, vent
pipe, and fittings are not supplied with the heater. Purchase these items at a local
hardware store.
Standard 4 inch
(10.16 cm) draft
regulator (required
if vent pipe ex-
ceeds 20 feet [6.1
meters] in length).
125 VENTILATION
Figure 4 - Ventilation Requirements
Review and understand the warnings in the Safety Informa-
tion Section. They are needed to safely operate this heater.
Follow all local codes when using this heater.
To Start Heater
1. Follow all ventilation and safety information.
2. Fill fuel tank with kerosene or No.1 fuel oil.
3. Attach fuel cap.
4. Plug power cord into standard 230 volt/50 hertz, grounded (earthed) outlet. Use an
extension cord if needed. Use only a three-wire, grounded (earthed) extension cord.
Extension Cord Wire Size Requirements
Up to 100 feet (30.5 meters) long, use 16 AWG (1.0 mm
101 to 200 feet (30.6 to 61 meters) long, use 14 AWG (1.5 mm
Heater will start when power cord is plugged into outlet. If not, push in flame-
out control reset button (see Figure 5).
Flame-Out
Control
Reset Button
(Fan Guard
Removed)
Figure 5 - Flame-Out Control Reset Button
!
WARNING
30" (76.2
cm) Mini-
mum
PFA/PV 023
!
WARNING
If horizontal run is
needed, use at least
1 foot (30.48 cm) rise
for each 10 feet (3.05
meters) of run.
2
) conductor
2
) conductor
Continued
7