Troubleshooting - Desa BLUE FLAME BLUE FLAME VENT-FREE NATURAL GAS HEATER Operation And Installation Manual

Blue flame vent-free natural gas heater 6000 btu manually controlled models
Table of Contents

Advertisement

VANGUARD 6000 BTU
NATURAL GAS HEATER

TROUBLESHOOTING

Note: All troubleshooting items are listed in
order of operation.
OBSERVED PROBLEM
When ignitor button is pressed, there is no
spark at ODS/pilot
When ignitor button is pressed, there is
spark at ODS/pilot but no ignition
ODS/pilot lights but flame goes out when
control knob is released
WARNING: Turn off heater and
let cool before servicing. Only a
qualified service person should
service and repair heater.
POSSIBLE CAUSE
1. Ignitor cable pinched or wet
2. Ignitor electrode not connected to igni-
tor cable
3. Piezo ignitor nut is loose
4. Broken ignitor cable
5. Ignitor electrode broken
6. Bad piezo ignitor
7. Ignitor electrode positioned wrong
1. Gas supply turned off or manual shutoff
valve closed
2. Control knob not in PILOT position
3. Control knob not pressed in while in PI-
LOT position
4. Air in gas lines when installed
5. ODS/pilot is clogged
6. Gas regulator setting is not correct
1. Control knob not fully pressed in
2. Control knob not pressed in long enough
3. Manual shutoff valve not fully open
4. Thermocouple connection loose at con-
trol valve
5. Pilot flame not touching thermocouple,
which allows thermocouple to cool,
causing pilot flame to go out. This prob-
lem could be caused by one or both of
the following:
A)
Low gas pressure
B)
Dirty or partially clogged ODS/
pilot
6. Thermocouple damaged
7. Control valve damaged
12
CAUTION: Never use a wire,
needle, or similar object to clean
ODS/pilot. This can damage ODS/
pilot unit.
REMEDY
1. Free ignitor cable if pinched by any
metal or tubing. Keep ignitor cable dry
2. Reconnect ignitor cable
3. Tighten nut holding piezo ignitor to
heater cabinet. Nut is located inside
heater cabinet at top
4. Replace ignitor cable
5. Replace ignitor
6. Replace piezo ignitor
7. Replace ignitor
1. Turn on gas supply or open manual
shutoff valve
2. Turn control knob to PILOT position
3. Press in control knob while in PILOT
position
4. Continue holding down control knob.
Repeat igniting operation until air is re-
moved
5. Clean ODS/pilot (see Cleaning and
Maintenance, page 11) or replace ODS/
pilot assembly
6. Replace gas regulator
1. Press in control knob fully
2. After ODS/pilot lights, keep control
knob pressed in 30 seconds
3. Fully open manual shut-off valve
4. Hand tighten until snug, then tighten 1/4
turn more
5. A) Contact local natural gas company
B) Clean ODS/pilot (see Cleaning and
Maintenance, page 11) or replace ODS/
pilot assembly
6. Replace thermocouple
7. Replace control valve
Continued