4 Installation Instructions

The HPL624 should be installed in accordance with the National Electrical Code and Local Authority Having
Jurisdiction.
1.
Mount the HPL624 Power Supply/Charger in the desired enclosure and location using supplied tape or optional
Snaptrack HST34. If mounted using screws, use #6 screws and 3/8" non-metallic spacer or supplied foam tape.
2.
The HPL624 is factory set for 12 VDC. Refer to preceding table to change to 6 VDC or 24 VDC output.
3.
Connect the proper transformer to terminals labeled [AC] (refer to preceding table for correct transformer selection).
4.
Use 18 AWG or larger wire for all power connections (battery, DC output).
IMPORTANT! Keep a minimum spacing of 0.25" (6.35 mm) between all power-limited and nonpower-limited
wiring such as the 115VAC/60Hz Input and the battery wiring.
5.
While carefully observing polarity, connect the devices to be powered to the terminals labeled [+ DC] and [DC -].
Note: To avoid potential damage, it is important to measure the output voltage prior to connecting any devices.
6.
Connect the battery using the supplied battery leads to the terminals labeled [BAT +] and [DC -].
Use two (2) 12 VDC batteries connected in series for 24 VDC operation.
Note: If batteries are not used, a loss of AC will result in a loss of output voltage.
7.
After batteries and AC power have been applied, both LEDs light.
8.
It is recommended that the output current be measured to ensure that it does not exceed the rated maximum current.

5 LED Indicators

Red (DC)
ON
ON
OFF
OFF

6 Terminal Identification

Terminal Label Function/Description
AC AC
– DC +
+ BAT –
For additional information:
• Visit our website at http://www.honeywellpower.com
• Contact Technical Support at (877) HPP-POWR
• E-mail us at hpp_techserv@honeywell.com
2
Green (AC) Power Supply Status
ON
Normal operating condition.
OFF
Loss of AC, Stand-by battery supplying power.
ON
No DC output. Short circuit or thermal overload condition.
OFF
No DC output. Loss of AC. Discharged or no battery present.
Low voltage AC input. (Refer to Voltage Output/Transformer Selection Table.)
6 VDC – 12 VDC @ 1.2 amps continuous supply current output.
24 VDC @ 750 mA continuous supply current output.
Stand-by battery connections. Maximum charge rate 500 mA.
HPL624 Power Supply/Charger — P/N 52263:C 1/10/08