Kenmore 33176 - Power Miser 12 Owner's Manual page 16

For potable water heating only not suitable for space heating not for use in mobile homes
Table of Contents

Advertisement

Forproper draft h ood attachment,
thedrafthood legs may
beangled s lightly i nward.
Place thedraft h ood legs inthereceiving holes onthetopof
thewater h eater. Thelegswillsnap intheholes togivea
tight f it.Secure t helegs ofthedraft h ood withthesupplied
draft h ood brackets.
Place t hevent p ipe over t hedraft h ood. With thevent p ipe in
position, drilla small holethrough b oththeventpipeand
draft h ood. Secure t hem together withasheet m etal screw,
seeFigure 18.
DP-J_FT HOOD
VENT,_
U
_
_
SCRE_
DP.AFT HOOD
,
,,
DRAFT
HOOD
'_
_'_]',_"-
VENT TO OUTDOORS
__,_
OR CHIMNEY
BRACKET
FIGURE
18.
Obstructed
or deteriorated
vent systems
may present
serious
health
risk or asphyxiation.
Breathing
Hazard - Carbon
Monoxide
Gas
.
Flue
gases
may
escape
if vent
_
":::1::_:-'_.;_.
pipe is not connected.
:,_f_'_
.
Do not store corrosive
chemicals
_:'_';"
in vicinity of water heater.
Chemical
corrosion
of flue
and
""
vent
system
can cause
serious
injury or death.
o Contact
a qualified
installer
or
service agency.
Breathing carbon monoxide can cause brain damage
or death. Always read and understand instruction manual.
Chemical
vapor
corrosion
of the flue
and vent
system
may
occur
if air for combustion
contains
certain
chemical
vapors.
Spray
can propellants,
cleaning
solvents,
refrigerator
and air
conditioner
refrigerants,
swimming
pool
chemicals,
calcium
and sodium
chloride,
waxes,
bleach
and process
chemicals
are typical
compounds
which
are potentially
corrosive.
Gas Piping
The vent
pipe from the water
heater
must be no less than
the
diameter
of the draft hood outlet
on the water
heater
and must
slope upward
at least 1/4 inch per linear foot (21 mm per meter),
see Figure
19.
S]
°
CHIMNEY
f
FIGURE 19.
Fire and Explosion
Hazard
• Do not use water
heater with
any
gas
other
than
the
gas
shown on the rating plate.
-Excessive
pressure
to
gas
control valve oar cause serious
injury or death.
• Turn
off
gas
lines
during
installation.
-Contact
qualified
installer
or
service agency.
All vent gases
must be completely
vented
to the outdoors
of the
structure
(dwelling).
Install
only the draft hood provided
with the
new water
heater
and no other draft hood.
Vent pipes must be secured
at each joint with sheet metal screws.
There
must
be a minimum
of 6 inches
(153
mm)
clearance
between
single
wall vent
pipe
and any combustible
material.
Fill and seal any clearance
between
single
wall vent pipe and
combustible
material
with
mortar
mix,
cement,
or other
noncombustible
substance.
For other
than
single
wall,
follow
vent pipe manufacturer's
clearance
specifications.
To insure
a
tight fit of the vent pipe in a brick chimney,
seal around
the vent
pipe with mortar
mix cement.
Make sure the gas supplied
is the same type listed on the model
rating
plate.
The
inlet
gas
pressure
must
not
exceed
14 inch water
column
(3.5kPa)
for natural
gas. The
minimum
inlet gas pressure
listed on the rating
plate is for the purpose
of
input
adjustment.
If the
gas
control
valve
is subjected
to
pressures
exceeding
1/2 pound
per square
inch (3.5kPa),
the
damage
to the gas control valve could result in a fire or explosion
from
leaking
gas.
If the main gas line shut-off serving
all gas appliances
is used, also
turn "OFF" the gas at each appliance.
Leave all gas appliances
shut "OFF" until the water heater installation
is complete.
Failure
to have
required
clearances
between
vent
piping
and
combustible
material
will result in a fire hazard.
Be sure
vent pipe
is properly
connected
to prevent
escape
of
dangerous
flue gases
which
could cause
deadly
asphyxiation.
A gas line of sufficient
size
must
be run to the water
heater.
Consult
the current
edition
of National
Fuel
Gas Code ANSI
Z223.1/NFPA
54 and your gas supplier
concerning
pipe size.
There
must be:
16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powermiser 12153.331760153.331770ha

Table of Contents