Introduction

Thank you for choosing DVPEN01-SL module. To correctly install and operate DVPEN01-SL, please read
the manual carefully before using the module.
DVPEN01-SL is an Ethernet communication module for remote setting and communication through
WPLSoft. DVPEN01-SL is able to send E-mails, automatically correct the RTC in DVP28SV11R/T and
exchange data. It supports Modbus TCP communication protocol and can conduct remote monitoring by using
SCADA (Supervisor Control and Data Acquisition) software or HMI (Human Machine Interfaces). DVPEN01-SL
can be the master of Modbus TCP, sending out Modbus TCP instructions and controlling the peripheral
equipment. In addition, under MDI/MDI-X auto-detection, it does not need to use a crossing cable. See the
contents below for more detailed instructions on DVPEN01-SL module.
1.1

Functions

Auto-detects 10/100Mbps transmission speed
MDI/MDI-X auto-detection
Supports Modbus TCP protocol (at the same time supports Master and Slave mode)
Able to send out E-mails
Auto-corrects the RTC in PLC through the Internet time correction function
Supports point-to-point data exchange (Max. data exchange length: 200 bytes)
1.2

Specifications

Internet interface
Item
Interface
Number of ports
Transmission method
Transmission cable
Transmission speed
Network protocol
Serial communication interface
Item
Interface
Number of ports
Transmission cable
Environment
Item
Noise immunity
Environment
DVP-PLC Operation Manual
Ethernet Communication Module DVPEN01-SL
RJ-45 with Auto MDI/MDIX
1 Port
IEEE802.3, IEEE802.3u
Category 5e
10/100 Mbps Auto-Detect
ICMP, IP, TCP, UDP, DHCP, SMTP, NTP, Modbus TCP
RS-232
1 Port
DVPACAB230, DVPACAB215, DVPACAB2A30, DVPACAB2B10
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2;
Specification
Specification