Download Print this page

Specifications - Omron G9SA Datasheet

Safety relay unit
Hide thumbs Also See for G9SA:

Advertisement

Specifications

Ratings
Power Input
Item
24 VAC/VDC:24 VAC, 50/60 Hz, or 24 VDC
Power supply voltage
100 to 240 VAC:100 to 240 VAC, 50/60 Hz
Operating voltage range
85% to 110% of rated power supply voltage
Power consumption
24 VAC/VDC: 1.8 VA/1.7 W max.
(See note.)
100 to 240 VAC: 9 VA max.
Note: When an Expansion Unit is connected, the power consumption is increased by 2 VA/2 W max.
Inputs
Item
Input current (See note.)
40 mA max.
Note: When an Expansion Unit is connected, the input current is increased by 30 mA max.
Contacts
G9SA-301/501/321-T#/TH301/EX301/EX031-T#
Item
Resistive load (cos φ =1)
Rated load
250 VAC, 5 A
Rated carry current
5 A
Characteristics
Item
Contact resistance (see note 1)
Operating time
Response time (see note 2)
Insulation resistance (see note 3)
Between different outputs
Between inputs and outputs
Dielectric
Between power inputs and outputs
strength
Between power inputs and other inputs
(only for 100 to 240-V models)
Vibration resistance
Destruction
Shock
resistance
Malfunction
Mechanical
Durability
Electrical
Minimum permissible load (reference value)
Ambient temperature
Ambient humidity
Terminal tightening torque
Weight (see note 4)
Approved standards
EMC
Note: 1. The contact resistance was measured with 1 A at 5 VDC using the voltage-drop method.
2. The response time is the time it takes for the main contact to open after the input is turned OFF.
3. The insulation resistance was measured with 500 VDC at the same places that the dielectric strength was checked.
4. Weight shown is for 24-VAC/VDC type. For 100 to 240-VAC type, add approximately 20 g.
G9SA
G9SA-301/TH301
G9SA-301/321-T#/TH301
G9SA-301/TH301
100 mΩ
30 ms max. (not including bounce time)
10 ms max. (not including bounce time)
100 MΩ min. (at 500 VDC)
2,500 VAC, 50/60 Hz for 1 min
10 to 55 Hz, 0.75-mm double amplitude
300 m/s
100 m/s
5,000,000 operations min. (at approx. 7,200 operations/hr)
100,000 operations min. (at approx. 1,800 operations/hr)
5 VDC, 1 mA
Operating:-25°C to 55°C (with no icing or condensation)
Storage:-25°C to 85°C (with no icing or condensation)
Operating:35% to 85%
Storage:35% to 85%
0.98 N·m
Approx. 210 g
EN954-1, EN60204-1, EN574 (-TH301), UL508, CSA C22.2 No. 14
EMI: EN55011 group 1 class A
EMS: EN50082-2 group 1
G9SA-501
24 VAC/VDC: 2.8 VA/2.6 W max.
100 to 240 VAC: 11 VA max.
G9SA-501
60 mA max.
G9SA-501/321-T#
2
2
Approx. 270 g
G9SA-321-T#
24 VAC/VDC: 3.5 VA/3.3 W max.
100 to 240 VAC: 12.5 VA max.
G9SA-EX301/EX031-T#
Approx. 130 g
G-111

Advertisement

loading