Download Print this page

Specifications - Omron G7S Datasheet

Safety relay

Advertisement

G7S

Specifications

Ratings
Operation Coil
Rated voltage
Rated current
24 VDC
30 mA
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23 C with tolerances of 15%.
2. Performance characteristics are based on a coil temperature of 23 C
3. The maximum voltage is based on an ambient operating temperature of 23 C maximum.
Switching Section (Contact Ratings)
Load
Rated load
Rated carry current
Maximum switching voltage
Maximum switching current
Maximum switching capacity (reference
value)
Min. permissible load
(See note.)
Contact material
Note: The above values are based on an operating frequency of 60 operations/min.
Characteristics
Contact resistance (See note 2.)
Operate time (See note 3.)
Release time (See note 3.)
Maximum operating
Mechanical
frequency
Rated load
Insulation resistance
Dielectric strength
Vibration
Destruction
Malfunction
Shock
Destruction
Malfunction
Life expectancy
Mechanical
Electrical
Ambient operating temperature
Ambient operating humidity
Ambient storage temperature
Ambient storage humidity
Weight
Note: 1. The values given above are initial values.
2. Measurement conditions: 5 VDC, 10 mA, voltage drops.
Characteristics of Safety Relay Socket
Model
Continuous current
6 A
P7S-14j
Note: Measurement conditions: Measurement of the same points as for the dielectric strength at 500 VDC.
2
Coil resistance
Must operate
voltage
800
80% max. (V)
Resistive load (cos
240 VAC: 3 A, 24 VDC: 3 A
6 A
250 VAC, 24 VDC
6 A
1,440 VA, 144 W
5 VDC, 10 mA
Ag ) Au
100 m max.
50 ms max.
50 ms max.
18,000 operations/hr
1,800 operations/hr
100 M min. (at 500 VDC)
2,500 VAC, 50/60 Hz for 1 min (1,500 VAC between contacts of same polarity)
10 to 55 Hz, 1.5-mm double amplitude
10 to 55 Hz, 0.75-mm double amplitude
2
1,000 m/s
(approx. 100G)
2
100 m/s
(approx. 10G)
10,000,000 operations min. (at approx. 18,000 operations/hr)
100,000 operations min. (at the rated load and approx. 1,800 operations/hr)
–10 C to 70 C (no icing)
35% to 85% RH
–25 C to 70 C (no icing)
35% to 85% RH
Approx. 65 g
Dielectric strength
2000 VAC for 1 min. between terminals
Must release
Max. voltage
voltage
10% min. (V)
110% (V)
=1)
Inductive load (cos
240 VAC: 3 A, 24 VDC: 1 A
3. Measurement conditions:
Rated voltage operation
Ambient operating temperature: 23 C
Does not include bounce time.
Insulation resistance
1000 M min. (see note)
G7S
Power
consumption
Approx. 0.8 W
= 0.4, L/R = 7 ms)