START-UP

Internal components and circuit boards of the drive are live
when the drive is connected to incoming power. Coming into
contact with this voltage is extremely dangerous and will result
in severe personal injury or death.
The motor terminals U, V, W and the DC-link terminals are
live when the drive is connected to incoming power, even if
the motor is not running.
Do not make any connections when the drive is connected to
the incoming power.
After having disconnected the drive, wait until all LEDs have
ceased emitting light. Wait 5 more minutes, and check for haz-
ardous voltage with volt meter, before doing any work on drive
connections. Do not even open the cover before this time has
expired.
Before connecting the drive to the incoming power, make sure
that the switchgear enclosure door is closed.
WARNING
The control I/O-terminals are isolated from the mains poten-
tial. However, the relay outputs and other I/O terminals may
have a dangerous control voltage present even when the drive
is disconnected from incoming power. Coming into contact
with this voltage could result in severe personal injury.
When working with the Connected Components Workbench
(CCW), never use the Rotate function as the motor will imme-
diately start and severe compressor damage could result.

Alternate Wire Lugs

See Table 1.
MODEL
FRAME SIZE
19MV
19XR6
a
NOTE(S):
a. Standard frame size for 19XR (consult jobsite drawing).
b. Customer connects to extruded bus bar using supplied L-brackets (up to 12 cables per phase).
DANGER
CAUTION
Table 1 — Wire Lugs
STANDARD
LUG
7
140G-M-TLA33
9
140G-R-TLC63
10
b

Verify Installation

Record the following job information:
1.
Job name
2.
Job number
3.
City
4.
State
5.
Zip code
Record the following nameplate information:
1.
From the Allen-Bradley nameplate (Fig. 1) located inside the
VFD enclosure:
a. Allen-Bradley ID or cat. no.
b. Allen-Bradley serial number
c. Carrier part number
NOTE: Additional nameplate data for 19MV is required for
VFD control of permanent magnet motor. This is not required
for induction motor as used for 19XR6/7.
2.
From the machine nameplate (Fig. 11 or 12) located inside
the VFD enclosure:
a. Chiller serial number
b. Chiller model
c. Motor rated load amps
d. Motor nameplate rpm
e. Motor nameplate kW
f. Motor nameplate voltage
g. Inverter PWM (pulse width modulation) frequency
h. Voltage
3.
From the drive module label located on the drive module:
a. Model or cat. number
b. Serial number
4.
From the HMI control panel screen:
a. Carrier part number and revision
b. Software number
STANDARD LUG
ALTERNATE
CABLE RANGE
ABB LUG
(3) 2/0-400 MCM
140G-M-TLA2A3
(6) 1/0-750 MCM
10
ALTERNATE LUG
CABLE RANGE
2x500-750