3.1.2 Restriction According to Mounting Directions

If the unit is used in a vertical orientation or installed in a horizontal orientation, note that the
ambient usage temperature should be as below.
Model name
Condition
Horizontally installed
GT707
Vertically used
Horizontally installed

3.1.3 Installation Space

Applicable panel thickness
A panel with a thickness of 1.0 to 5.0 mm should be used. Use a panel that is strong enough
not to be warped.
Clearance when the GT is installed
When installing the GT unit, if other parts are being installed to the panel or cables are being
wired to it, we recommend providing a clearance around the GT unit. This prevents cables
from being damaged, and facilitates the installation work. Also, make sure that the slits in the
main unit are never obstructed.
Model name
Clearance
30 mm or more
GT707
(50 mm or more recommended)

3.1.4 Mounting Screws

The GT unit is secured to the installation panel using the fittings and screws (4 sets/per unit)
provided with the unit.
Commercial M3 screws (length: 16 mm) can be also used. Using screws that do not comply
with the specifications will cause failures such as decrease of water-proof property.
Ramco Innovations
Ambient
temperature
0 to 50 C
Vertically used
Clearance on the surface to connect
the screen transfer cable
60 mm
www.panasonicsensors.com