Reset After Using Start-Up Assistant - Carrier 48TC 07 Installation, Start-Up And Service Instructions Manual

Variable frequency drive (vfd) factory-installed option 2-speed motor control for 2-stage cooling rooftop units
Hide thumbs Also See for 48TC 07:
Table of Contents

Advertisement

Reset After Using Start-Up Assistant

CAUTION
CONFIGURATION OVERRIDE HAZARD
Do not use ABB or Carrier start-up assistant on this VFD
application. Use of start-up assistant will override the factory
VFD configurations.
The following section details how to reset the VFD after acciden-
tally using Start-Up Assistant.
When the VFD has been incorrectly programmed by using Start-
Up Assistant, the drive may be locked in an override loop because
of motor ID Run Fail (error code 11) and First Start (error
code 2025).
Use the following procedure to reset the factory configurations for
ACS320 VFDs:
1.
Disconnect unit power. Lock-out/tag out.
2.
Remove the VFD's terminal cover.
3.
Disconnect the D11 input at terminal 12. The terminals are
numbered on the bottom of the block (see Fig. 55 for the
location of terminal block that contains terminal 12).
4.
Connect the VFD Keypad accessory to the VFD (if not
already connected).
NOTE: The VFD Keypad is a field-installed accessory; it is
not included with the factory-installed VFD option.
5.
Go immediately to parameter 1705 OVERRIDE ENABLE
and select "Off".
Fig. 55 — ACS320 Terminal Blocks
6.
At this point, providing you have a clean backup of the
drive, you can select "DOWNLOAD FULL SET" from
"PAR BACKUP" from the Main Menu. If you do not have
a clean backup the drive will have to be manually pro-
grammed following the instructions in this document.
7.
When the correct parameters have been uploaded, discon-
nect power to the unit, reconnect DI1 to Terminal 12, and
replace the terminal cover.
8.
Reconnect power to the unit. The VFD is now commis-
sioned from the backup file.
TERMINALS
9 – 16
Use the following procedure to reset the factory configurations for
ACH550 VFDs:
1.
Disconnect unit power. Lock-out/tag-out.
2.
Remove the VFD's front cover (see Fig. 39 on page 30).
3.
Disconnect the DI1 input at Terminal 13 (see Fig. 56 for
location of DI1).
4.
Connect the VFD Keypad accessory to the VFD (if not
already connected).
NOTE: The VFD Keypad is a field-installed accessory; it is
not included with the factory-installed VFD option.
5.
With the wire disconnected, use the keypad to stop the
loop and enter "358" in parameter 1704 OVERRIDE
PASS CODE.
6.
Go immediately to parameter 1705 OVERRIDE ENABLE
and select "Off".
7.
At this point, providing you have a clean backup of the
drive, you can select "DOWNLOAD FULL SET" from
"PAR BACKUP" from the Main Menu.
8.
If you do not have a clean backup the drive will have to be
manually programmed following the instructions in this
document.
9.
When the correct parameters have been uploaded, discon-
nect power to the unit, reconnect DI1 to Terminal 13, and
replace the VFD cover.
10. Reconnect power to the unit. The VFD is now commis-
sioned from the backup file.
TERMINALS
10 – 18
Fig. 56 — Terminal Block Location on ACH550 VFD
68