Pre-Start Check, Sav™ Option - Carrier 48TC 07 Installation, Start-Up And Service Instructions Manual

Variable frequency drive (vfd) factory-installed option 2-speed motor control for 2-stage cooling rooftop units
Hide thumbs Also See for 48TC 07:
Table of Contents

Advertisement

Table 10 — 40RUQ Min cfm Per Fan Motor Type
SINGLE SPEED
MODEL-SIZE
FAN MOTOR
40RUQ 07
1800
40RUQ 08
2250
40RUQ 12
3000
40RUQ 16
4500
40RUQ 25
6000
Fig. 6 — ACS320 VFD Location for the following units: 48/50TC 07 and 50TCQ 07
2-SPEED FAN
2-SPEED FAN
MOTOR (AT
MOTOR (AT
HIGH SPEED)
LOW SPEED)
2030
1338
2535
1673
3380
2231
4500
2970
6000
3960
(208/230V and 460V units only)
Pre-Start Check, SAV™ Option
1.
Remove the access panel to reach the VFD.
48/50 Series: Blower compartment panel
40RU: Rear access panel
NOTE: See Fig. 6-23 for VFD location in the units covered
by this document.
2.
Read all safety, caution and warning labels.
3.
Inspect wiring at the VFD for loose or disconnected wires
at the terminal strip and for wires in contact with sharp
edges and moving parts (pulley, belt).
Variable
Frequency
Drive (VFD)
5