The following checks shall be applied to installations using flammable
refrigerants:
the charge size is in accordance with the room size within which the refrigerant
containing parts are installed;
the ventilation machinery and outlets are operating adequately and are not
obstructed;
if an indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant;
marking to the equipment continues to be visible and legible. Markings and signs
that are illegible shall be corrected;
refrigeration pipe or components are installed in a position where they are unlikely
to be exposed to any substance which may corrode refrigerant containing
components, unless the components are constructed of materials which are
resistant to being corroded or are suitably protected against being so corroded.
Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimised. For repair to
the refrigerating system, IEC60335-2-40:2018 Annex DD.4.3 to DD.4.7 shall be
completed prior to conducting work on the system.
Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of
a flammable gas or vapour being present while the work is being performed.
General work area
All maintenance staff and others working in the local area shall be instructed on the
nature of work being carried out. Work in confined spaces shall be avoided.