B-Refrigerant Charge and Check - Fin/Tube Coil
WARNING - Do not exceed nameplate charge under
any condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant,
reclaim the charge, evacuate the system, and add required
nameplate charge.
NOTE - System charging is not recommended below 60°F
(15°C). In temperatures below 60°F (15°C) , the charge
must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in standard cooling mode.
1 - Attach gauge manifolds and operate unit in cool-
ing mode with economizer disabled until system
stabilizes (approximately five minutes). Make sure
outdoor air dampers are closed.
2 - Check each system separately with all stages
operating.
3 - Use a thermometer to accurately measure the out-
door ambient temperature.
4 - Apply the outdoor temperature to TABLE 10 to
TABLE 13 to determine normal operating pressures.
Pressures are listed for sea level applications at
80°F dry bulb and 67°F wet bulb return air.
5 - Compare the normal operating pressures to the
pressures obtained from the gauges. Minor varia-
tions in these pressures may be expected due to
differences in installations. Significant differences
could mean that the system is not properly charged
or that a problem exists with some component in
the system. Correct any system problems before
proceeding.
6 - If discharge pressure is high, remove refrigerant
from the system. If discharge pressure is low, add
refrigerant to the system.
• Add or remove charge in increments.
• Allow the system to stabilize each time refriger-
ant is added or removed.
7 - Use the following approach method along with the
normal operating pressures to confirm readings.
TABLE 10 581129-01
KGC/KCC092S Fin/Tube - W & W/O Reheat
Outdoor
CIRCUIT 1
Coil
Discharge
Entering
+ 10 psig
Air Temp
65°F
270
75°F
310
85°F
352
95°F
401
105°F
453
115°F
511
CIRCUIT 2
Suction
Discharge
Suction
+ 5 psig
+ 10 psig
+ 5 psig
128
255
131
295
133
338
136
388
140
433
145
488
KGC/KCC102S Fin/Tube - W & W/O Reheat
Outdoor
Coil
Entering
Air Temp
65°F
75°F
85°F
95°F
105°F
115°F
KGC/KCC120S Fin/Tube - W & W/O Reheat
Outdoor
Coil
Entering
Air Temp
65°F
75°F
85°F
95°F
105°F
115°F
KGC/KCC150S Fin/Tube - W & W/O Reheat
Outdoor
Coil
Entering
Air Temp
65°F
75°F
85°F
95°F
105°F
115 °F
Charge Verification - Approach Method - AHRI Testing
(Fin/Tube Coil Continued)
1 - Using the same thermometer, compare liquid tem-
perature to outdoor ambient temperature.
Approach Temperature = Liquid temperature (at
condenser outlet) minus ambient temperature.
2 - Approach temperature should match values in
TABLE 14. An approach temperature greater than
value shown indicates an undercharge. An approach
temperature less than value shown indicates an
overcharge.
140
3 - The approach method is not valid for grossly over
146
or undercharged systems. Use TABLE 10 to TABLE
151
13 as a guide for typical operating pressures.
155
160
162
Page 33
TABLE 11 581130-01
CIRCUIT 1
Discharge
Suction
Discharge
+ 10 psig
+ 5 psig
+ 10 psig
269
128
308
132
350
135
396
139
447
141
502
146
TABLE 12 581131-01
CIRCUIT 1
Discharge
Suction +
Discharge
+ 10 psig
5 psig
+ 10 psig
263
125
301
125
341
123
386
125
440
130
492
139
TABLE 13 581132-01
CIRCUIT 1
Discharge
Suction +
Discharge
+ 10 psig
5 psig
+ 10 psig
281
121
320
125
364
129
407
132
456
135
508
139
CIRCUIT 2
Suction
+ 5 psig
276
138
314
142
359
146
407
149
458
152
513
156
CIRCUIT 2
Suction +
5 psig
262
132
304
140
348
146
394
152
447
156
499
158
CIRCUIT 2
Suction +
5 psig
283
137
325
141
370
143
415
145
464
148
517
151