Table 17 — HH57AC081 Sensor Wiring Terminations
TERMINAL
NUMBER
LABEL
1
S-BUS
2
S-BUS
Use Fig. 84 and Table 18 to set the DIP switches for the desired
use of the sensor.
Table 18 — HH57AC081 Sensor DIP Switch
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
USE
1
DA
OFF
RA
ON
OA
OFF
NOTE: When a S-Bus sensor is connected to an existing network,
it will take 60 minutes for the network to recognize and auto-con-
figure itself to use the new sensor.
During the 60 minute setup period, no alarms for sensor failures
(except SAT) will be issued and no economizing function will be
available.
CO
SENSOR WIRING
2
When using a CO
sensor, the black and brown common wires are
2
internally connected and only one is connected to "IAQ COM" on
the W7220. Use the power from the W7220 to power the CO
sensor OR make sure the ground for the power supplies are com-
mon. See Fig. 85 for CO
sensor wiring.
2
CO Sensor
24V
+
Analog
Out
1
Power supply. Provide disconnect
means and overload protection
as required.
Fig. 85 — CO
INTERFACE OVERVIEW
This section describes how to use the EconoMi$er
face for:
Keypad and menu navigation
Settings and parameter changes
Menu structure and selection
USER INTERFACE
The user interface consists of a 2-line LCD display and a 4-button
keypad on the front of the economizer controller.
TYPE
DESCRIPTION
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
2
3
ON
OFF
OFF
OFF
OFF
OFF
Red
L1
(Hot)
Black
L2
1
Yellow
Brown
Orange
Green
Sensor Wiring
2
X user inter-
®
Keypad
The four navigation buttons (see Fig. 86) are used to scroll
through the menus and menu items, select menu items, and to
change parameter and configuration settings.
To use the keypad when working with menus:
Press the ▲ (Up arrow) button to move to the previous menu.
Press the ▼ (Down arrow) button to move to the next menu.
Press the
(Enter) button to display the first item in the
currently displayed menu.
Menu Up
Menu Up
Menu Up
(Exit)
(Exit)
(Exit)
Scroll
Scroll
Scroll
Button
Button
Button
Up/Down
Up/Down
Up/Down
Buttons
Buttons
Buttons
Fig. 86 — W7220 Controller Navigation Buttons
Press the
(Menu Up/Exit) button to exit a menu's item and re-
turn to the list of menus. To use the keypad when working with Set
2
Points, System and Advanced Settings, Checkout tests and Alarms:
1.
Navigate to the desired menu.
2.
Press the
(Enter) button to display the first item in the
currently displayed menu.
3.
Use the ▲ and ▼ buttons to scroll to the desired parameter.
4.
Press the
(Enter) button to display the value of the
currently displayed item.
5.
Press the ▲ button to increase (change) the displayed
parameter value.
6.
Press the ▼ button to decrease (change) the displayed
parameter value.
NOTE: When values are displayed, pressing and holding the
▲ or ▼ button causes the display to automatically increment.
7.
Press the
(Enter) button to accept the displayed value
and store it in nonvolatile RAM.
8.
"CHANGE STORED" displays.
9.
Press the
(Enter) button to return to the current menu
parameter.
10. Press the
(Menu Up/Exit) button to return to the previous
menu.
Menu Structure
Table 19 illustrates the complete hierarchy of menus and parame-
ters for the EconoMi$er
The Menus in display order are:
STATUS
SET POINTS
SYSTEM SETUP
ADVANCED SETUP
CHECKOUT
ALARMS