Troubleshooting - Carrier 40MBFAQ Service Manual

Floor console ductless system size 12k
Hide thumbs Also See for 40MBFAQ:
Table of Contents

Advertisement

40MBFAQ: Service Manual

TROUBLESHOOTING

This section provides the required flow charts to troubleshoot problems
that may arise.
NOTE: Information required in the diagnoses can be found either on
the wiring diagrams or in the "APPENDICES" on page 49.
Required Tools:
The following tools are needed when diagnosing the units:
• Digital multimeter
• Screw drivers (Phillips and straight head)
• Needle−nose pliers
• Refrigeration gauges
Recommended Steps
1. Refer to the diagnostic flowcharts, see Table 6 on page 14 and
determine the problem at hand.
2. Go to the chart, see "DIAGNOSIS AND SOLUTION" on page 15
and follow the steps in the chart for the selected problem.
For ease of service, systems are equipped with diagnostic code display
LED's on both the indoor and outdoor units. The outdoor diagnostic
display is on the outdoor unit board and is limited to very few errors.
The indoor diagnostic display is a combination of flashing LED's on the
display panel on the front of the unit. If possible always check the
diagnostic codes displayed on the indoor unit first. The diagnostic codes
for the indoor and outdoor units are listed in the appendix (see
"APPENDICES" on page 49.
Safety
Electricity remains in the capacitors even when the power supply is shut off. Do not forget to discharge the electricity in the capacitor.
For other models, connect discharge resistance (approx.100Ù 40W) or soldering iron (plug) between +, - terminals of the electrolytic capacitor on the
contrary side of the outdoor PCB.
NOTE: Figure 17 is for reference only.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Problems may occur that are not covered by a diagnostic code, however
are covered by the diagnostic flow charts. These problems are typical air
conditioning mechanical or electrical issues that can be corrected using
standard air conditioning repair techniques.
For problems requiring measurements at the control boards, note the
following:
1. Always disconnect the main power.
2. When possible check the outdoor board first.
3. Start by removing the outdoor unit top cover.
4. Reconnect the main power.
5. Probe the outdoor board inputs and outputs with a digital multi-
meter referring to the wiring diagrams.
6. Connect the red probe to hot signal and the black probe to the ground
or negative.
7. Note that some of the DC voltage signals are pulsating voltages for
signal. this pulse should be rapidly moving at all times when there is
a signal present.
8. If it is necessary to check the indoor unit board you must start by
disconnecting the main power.
9. Next remove the front cover of the unit and then control box cover.
10. Carefully remove the indoor board from the control box, place it
face up on a plastic surface (not metal).
11. Reconnect the main power and repeat steps 5, 6, and 7.
12. Disconnect main power before reinstalling board to avoid shock
hazard and board damage.
Electrolytic Capacitors
(HIGH VOLTAGE! CAUTION!)
Fig. 16 — Capacitors
Fig. 17 — Discharging Position
13
A220989