Storage and Charge Maintenance Guide
1.
Receipt of your battery
1.1. Your N1C LR-Series lithium battery leaves the factory with approximately 30% State of
Charge (SOC).
1.2. Your N1C LR-Series battery module should be installed within 30 days of receipt. If
unable to install in this time period, please follow the charge procedure in the following
pages within 30 days of receipt.
1.3. The SOC of your battery can be viewed without installing the battery or connecting it to
your N1C UPS. To view your battery SOC simply open the box to expose the battery
breaker on the rear of the module, turn on the breaker (flip up), and press and hold
the button on the front of the battery module for 4-5 seconds. The Fault light should
blink red, and there should be 1-4 green status lights lit. Each lit light represents
approximately 25% SOC. NOTE: If your battery has one solid red light and one solid
green light it is in Low Voltage Protection Mode and will need to be returned to and
N1C Service Center for recharging.
1.4. NOTE: To discharge the battery module connect to UPS with load or use integrated
solution in 5.1.
2. Battery Storage
2.1. N1C battery modules should be stored at a SOC greater than 60%. Any time not
connected to an N1C UPS is considered storage.
Storage time, temperature, and
humidity when stored at 60%
SOC
N1C LR-Series Battery Module
32F~77F <12 months
77F~110F <3 months
110F~120F <1 month
32F~77F is the recommended storage temperature
Max. 95%RH
Max. 95%RH
Max. 95%RH

Advertisement

loading

Summary of Contents for N1C LR Series

  • Page 1 1.3. The SOC of your battery can be viewed without installing the battery or connecting it to your N1C UPS. To view your battery SOC simply open the box to expose the battery breaker on the rear of the module, turn on the breaker (flip up), and press and hold the button on the front of the battery module for 4-5 seconds.
  • Page 2 3. Charge Procedure using N1C UPS 3.1. N1C LR-Series battery modules should only be connected to LR-Series N1C UPS systems. Connection to any other equipment will void warranty and may be hazardous. 3.2. Connection Steps: 3.2.1. Connect UPS to the battery module (CON 1 or CON 2) with supplied battery cable.
  • Page 3 3.2.3. Set the ID switch dial to the “0” position. 3.2.4. Turn the battery breaker from OFF to ON (lift up). 3.2.5. Press the button on the front of the battery module for 5s to wake up the battery.
  • Page 4 3.2.6. Insert the supplied Termination Cable in to either Extension Port on the battery. 3.3. Charging Procedure 3.3.1. Start Charging: After the battery module is connected as above to the UPS, connect AC power to the UPS to start charging. 3.3.2.
  • Page 5 COM BMS cable is connected properly and/or the ID dial is set to “0”. NOTE: If your battery has one solid red light and one solid green light it is in Low Voltage Protection Mode and will need to be returned to and N1C Service Center for recharging.
  • Page 6 Termination RJ11 shorting plug Cable 4.2. Install the short RJ11 Termination Cable in to one of the Extension Ports on the back of the battery module. 4.3. Set the DC source with a constant current (CC): 15A; Constant voltage (CV): 52.5; then turn off...
  • Page 7 34.5V, then let rest 15 minutes. NOTE: SOC 30% is approximately 48.5VDC. 5.4. To recharge to 80%SOC, set constant current (CC): 50A; Constant voltage (CV): 52.5V, termination current: 5A. Charge time to 80% SOC for N1C.L4850EBM2U: approx. 95 minutes. Charge time to 80% SOC for N1C.L48100EBM3U: approx. 190 minutes.

This manual is also suitable for:

N1c.l48100ebm3uN1c.l4850ebm2u