Storage and Charge Maintenance Guide
1.
Receipt of your battery
1.1. Your N1C LR-Series lithium battery leaves the factory with approximately 30% State of
Charge (SOC).
1.2. Your N1C LR-Series battery module should be installed within 30 days of receipt. If
unable to install in this time period, please follow the charge procedure in the following
pages within 30 days of receipt.
1.3. The SOC of your battery can be viewed without installing the battery or connecting it to
your N1C UPS. To view your battery SOC simply open the box to expose the battery
breaker on the rear of the module, turn on the breaker (flip up), and press and hold
the button on the front of the battery module for 4-5 seconds. The Fault light should
blink red, and there should be 1-4 green status lights lit. Each lit light represents
approximately 25% SOC. NOTE: If your battery has one solid red light and one solid
green light it is in Low Voltage Protection Mode and will need to be returned to and
N1C Service Center for recharging.
1.4. NOTE: To discharge the battery module connect to UPS with load or use integrated
solution in 5.1.
2. Battery Storage
2.1. N1C battery modules should be stored at a SOC greater than 60%. Any time not
connected to an N1C UPS is considered storage.
Storage time, temperature, and
humidity when stored at 60%
SOC
N1C LR-Series Battery Module
32F~77F <12 months
77F~110F <3 months
110F~120F <1 month
32F~77F is the recommended storage temperature
Max. 95%RH
Max. 95%RH
Max. 95%RH