Routing the cables

MANUFACTURED IN 20XX J
When you route the cables:
Install the AC power cables and the control cables on separate routes.
Use metallic screen cables for control cables.
Do not put extra cables through the MVS without permission.
For more information, see drawing 3AES-PVS-100_120-MVS-01-DW02.
1
2
3
1
Ground
2
Inverters cable entry
3
Control cable entry (second option)
4
Control cable entry
5
MV cable entry

Earthing

Always construct an earthing electrode for the MVS. Always follow the local regulations.
Follow the minimum requirements for the earthing electrode:
Minimum cross-sectional area = 95 mm
Installation depth = 500...800 mm from the surface of the soil
Installation route around the MVS = one meter from the outer wall
Connect the MVS earthing busbar and the station enclosure to the earthing electrode.
Use joint lubricant to protect the connection point against corrosion
For more information, see drawing 3AES-PVS-100_120-MVS-02-DW02.