Comfort Alert Module; Energy Management System Relay; Smart Start Assist; Ssa Specifications - Bosch Greensource CDi Series Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

24 | Options

Comfort Alert Module

The Comfort Alert diagnostics module (CADM) is a
breakthrough innovation for troubleshooting heat pump
system failures. (Figure #55)
Figure # 55
B
y monitoring and analyzing data from the compressor
and the thermostat demand, the module can accurately
detect the cause of electrical and system related failures
without any sensors. A flashing LED indicator
communicates the ALERT code and guides the service
technician more quickly and accurately to the root cause
of a problem.
This module does not provide safety protection! The
Comfort Alert module is a monitoring device and
cannot shut down the compressor directly.
When an abnormal system condition occurs, the
Comfort Alert module displays the appropriate ALERT
and/or TRIP LED. The yellow ALERT LED will flash a
number of times consecutively, pause and then repeat
the process.
To identify a Flash Code number, count the number of
consecutive flashes. Every time the module powers up,
the last ALERT Flash Code that occurred prior to shut
down is displayed for one minute.

Energy Management System Relay

The factory installed Energy Management System Relay
can be used by individual commercial and/or residential
entities to monitor, measure and control their electrical
building load needs. This is accomplished by energizing
and de-energizing the relay coil which opens and closes
the relay contacts that are in series with the low voltage
output of the unit transformer and the input of the UPM
board.Energy
8733942411 (2017/07)

Smart Start Assist

SM series are available with the Smart Start Assist
device as either a factory installed option or a field
installed accessory. This device reduces starting (in-
rush) current for compressors by 45% to 65%. This
reduction in starting current can eliminate or greatly
reduce "light flickering" during compressor starts and
can reduce the required size of back-up transformers.
The adaptive technology of the device can also extend
compressor life by providing smoother, lower currents
starts and by protecting the compressor from transient
over voltage and under voltage after ramp up.
The Smart Start is designed for single phase scroll
compressors and can also optimize algorithms for high
pressure starts. SSA as showed in figure #56.
Mounting Plate

SSA Specifications

Rated Operational Voltage:
Environmental Operating
Range:
Degree of Protection:
Overvoltage:
Operational Rated Current:
Max Starting Current:
Min Full Load Current:
Min time between starts:
Min time between stop to
start:
Subject to change without prior notice
SM Series Heat Pump
Smart Start Assist
Figure # 56
208/230VACrms +/- 15% 50-60 Hz
-4° to 149°F (-20° to 65°C); < 95% @
40 C relative humidity, non-con-
densing
IP20
Category II
32 Amps
80A ACrms
80A ACrms
6 minutes
3 minutes
SM Series Heat Pump

Advertisement

Table of Contents
loading

Table of Contents