10 | Comfort Alert Module

set to 4) within an hour the UPM controller will
enter into a hard lockout condition. It will
constantly monitor the refrigerant temperature
with the sensor mounted close to the
evaporator between the thermal expansion
valve and evaporator coil as shown in Figure
#4. If temperature drops below or remains at
the freeze limit trip for 30 seconds, the
controller will shut the compressor down and
enter into a soft lockout condition. Both the
status LED and the Alarm contact will be
active. The LED will flash (three (6) times) the
code associated with this alarm condition. If
this alarm occurs 2 times (or 4 if Dip switch is
set to 4) within an hour the controller will enter
into a hard lockout condition.
Refer to page #10 for more information.
Freeze sensor will not guard against loss of
water. Flow switch is recommended to
prevent unit from running, if water flow is
lost or reduced.
INTELLIGENT RESET: If a fault condition is
initiated, the 5 minute delay on break time
period is initiated and the unit will restart after
these delays expire. During this period the
fault LED will indicate the cause of the fault. If
the fault condition still exists or occurs 2 or 4
times (depending on 2 or 4 setting for Lockout
dip switch) before 60 minutes, the unit will go
into a hard lockout and requires a manual
lockout reset. A single condensate overflow
fault will cause the unit to go into a hard
lockout immediately, and will require a manual
lockout reset.
LOCKOUT RESET: A hard lockout can be reset
by turning the unit thermostat off and then
back on when the "RESET" dip switch is set to
"Y" or by shutting off unit power at the circuit
breaker when the "RESET" dip switch is set to
"R".
The blower motor will remain active during a
lockout condition.
8 733 920 847 (2014/01)
COMFORT ALERT MODULE
The Comfort Alert diagnostics module (CADM) is a
breakthrough innovation for troubleshooting heat
pump system failures. (Figure #9)
By monitoring and analyzing data from the
compressor and the thermostat demand, the
module can accurately detect the cause of
electrical and system related failures without any
sensors. A flashing LED indicator communicates
the ALERT code and guides the service technician
more quickly and accurately to the root cause of a
problem.
This module does not provide safety protection!
The Comfort Alert module is a monitoring device
and cannot shut down the compressor directly.
When an abnormal system condition occurs, the
Comfort Alert module displays the appropriate
ALERT and/or TRIP LED.
The yellow ALERT LED will flash a number of times
consecutively, pause and then repeat the process.
To identify a Flash Code number, count the
number of consecutive flashes.
Every time the module powers up, the last
ALERT Flash Code that occurred prior to shut
down is displayed for one minute.
Subject to change without prior notice
LM CS Series Heat Pump
Figure # 9
LM CS Series Heat Pump