Power Supply - Siemens SIMATIC MICRO-DRIVE PDC600 Equipment Manual

Servo drive system
Table of Contents

Advertisement

2.3

Power supply

Infeed points
You supply the PDC at the logic unit (1L+, 2L+) and power unit (4L+) infeed points with the
following voltages:
Table 2-1
Supply voltage of PDC
Infeed
Nominal sup‐
points
ply voltage
Logic unit
24 V DC
1L+, 2L+
Power unit
24 to 48 V DC
4L+
When energy recovery is activated, a supply voltage above 52.8 V DC (maximum value
1)
58.8 V) is also permitted. Use a suitable bi-directional supply to ensure that the voltage at
4L+ never exceeds 60 V DC during operation or under fault conditions.
It is essential that you observe the information on recovery in the section "Energy
recovery" in the System Manual SIMATIC MICRO-DRIVE Drive controller PDC
support.industry.siemens.com/cs/ww/en/view/109797859).
Use separate power supply units to supply the logic unit and the power unit or a filter between
the shared power supply unit and the power supply.
NOTICE
If you are using SELV/PELV with a common negative pole for the supply of 1L+ and 4L+, you
must insert a two-pole miniature circuit breaker (2P, 240 V AC, tripping characteristic C, rated
current 3 A, EN 60947-2) according to UL category DIVQ (UL 498) in the supply line to 1M/1L+.
You can find the article numbers of the miniature circuit breakers to be used in the section
"Accessories/Spare parts" in the System Manual SIMATIC MICRO-DRIVE Drive controller PDC
(https://support.industry.siemens.com/cs/ww/en/view/109797859).
PDC600(F)
Equipment Manual, 12/2023, A5E50502703-AB
Static supply
voltage
19.2 to 28.8 V
16.8 to 52.8 V
1)
WARNING
Dynamic supply
Maximum voltage
voltage
under fault condi‐
tions (power supply)
for maintaining elec‐
trical and functional
safety
18.5 to 30.2 V
Max. 42.4 V
Non-periodic over‐
voltage max. 35 V
for max. 500 ms
with a recovery time
of 50 s
16.8 to 52.8 V
1)
Max. 60 V
Product overview
2.3 Power supply
Fusing
Internal fusible link, not
replaceable by user.
Fusing on installation
side necessary for
through-wiring!
Installation-side two-
pole protection for
1L+/1M for SELV/PELV
with common negative
pole required for the sup‐
ply of 1L+ and 4L+.
Two-pole miniature cir‐
cuit breaker
Two-pole miniature cir‐
cuit breaker
(https://
15