[ IX Troubleshooting ]
1. Error Code
7100
Total capacity error
2. Error definition and error detection method
The model total of indoor units in the system with one heat source unit exceeds limitations.
3. Error source, cause, check method and remedy,
Error source
Heat source
(1)
The model total of indoor units in the sys-
unit
tem with one heat source unit exceeds the
following table.
(2)
The model selection switches (SW5-3 - 5-
6) on the heat source unit are set incor-
rectly.
(3)
The heat source unit and the auxiliary unit
(OS) that is connected to the same system
are not properly connected.
HWE15150
Cause
<PQHY>
Capacity Total
Model
P72 model
93
P96 model
124
P120 model
156
P144 model
187
P168 model
218
P192 model
249
P216 model
280
P240 model
312
P264 model
343
P288 model
374
P312 model
405
P336 model
436
P360 model
468
<PQRY>
Capacity Total
Model
P72 model
108
P96 model
144
P120 model
180
P144 model
216
P168 model
252
P192 model
288
P216 model
324
P240 model
360
P264 model
396
P288 model
432
P312 model
468
P336 model
504
SW5
Model
3
4
5
6
72 model
OFF ON
OFF OFF
96 model
ON
ON
OFF
OFF
120 model
OFF
OFF
ON
OFF
144 model
ON
ON
ON
OFF
168 model
OFF
OFF
OFF
ON
192 model
ON
OFF
OFF
ON
- 295 -
Check method and remedy
1)
Check the model total (capacity code total) of
units connected.
2)
Check the model name (capacity code) of the
connected indoor unit set by the switch (SW2 on
indoor unit board).
When the model name set by the switch is differ-
ent from that of the unit connected, turn off the
power source of the heat source and the indoor
units, and change the setting of the model name
(capacity code).
Check the setting for the model selection switch
on the heat source unit (Dipswitches SW5-3 - 5-
6 on the heat source unit control board).
Confirm that the TB3 on the OC and OS are
properly connected.