[ VIII Test Run Mode ]
4. Amount of refrigerant to be added <PQRY>
The amount of refrigerant that is shown in the table below is factory-charged to the heat source units.
The amount necessary for extended pipe (field piping) is not included and must be added on site.
Heat source unit model
Amount of pre-charged refrigerant
in the heat source unit (kg)
Amount of pre-charged refrigerant
in the heat source unit [lbs]
(1) Calculation formula
The amount of refrigerant to be added depends on the size and the length of field piping. (unit in m[ft])
Amount of added refrigerant (kg) = (0.36 x L
Amount of added refrigerant (oz) = (3.88 x L
L
: Length of ø28.58[1-1/8"] high pressure pipe (m)
1
L
: Length of ø22.2[7/8"] high pressure pipe (m)
2
L
: Length of ø19.05[3/4"] high pressure pipe (m)
3
L
: Length of ø15.88[5/8"] high pressure pipe (m)
4
L
: Length of ø15.88[5/8"] liquid pipe (m)
5
L
: Length of ø12.7[1/2"] liquid pipe (m)
6
L
: Length of ø9.52[3/8"] liquid pipe (m)
7
L
: Length of ø6.35[1/4"] liquid pipe (m)
8
,
' ,
1, 2, 3, 4
1
Amount for the BC
controllers (main/sub)
Heat source unit
total index
(kg)
1
P72
P96
P120
P144
3.0
P168
P192
P216
P240
When connecting PLFY-P08NBMU-E2, add 0.3kg of refrigerant per indoor unit.
Round up the calculation result to the nearest 0.1kg. (Example: 18.04kg to 18.1kg)
Round up the calculation result in increments of 4oz (0.1kg) or round it up to the nearest 1oz. (Example: 78.21oz to 79oz)
HWE15150
P72
P96
5.0
5.0
11.0
11.0
) + (0.23 x L
1
+ (0.12 x L
) + (0.06 x L
) + (0.024 x L
6
7
' ) + (2.48 x L
1
+ (1.30 x L
' ) + (0.65 x L
6
7
' ,
' ,
' : Refer to the table below.
2
3
4
BC controller (Main)
' (oz)
HA TYPE
1
1
BC controller (sub)
Total number of BC
106
1
2
P120
P144
P168
5.0
6.0
11.0
13.2
) + (0.16 x L
) + (0.11 x L
2
3
) +
+
+
+
8
1
2
3
' ) + (1.73 x L
' ) + (1.19 x L
2
3
' ) + (0.26 x L
' ) +
' +
' +
8
1
2
L
' : Length of ø28.58[1-1/8"] high pressure pipe [ft]
1
L
' : Length of ø22.2[7/8"] high pressure pipe [ft]
2
L
' : Length of ø19.05[3/4"] high pressure pipe [ft]
3
L
' : Length of ø15.88[5/8"] high pressure pipe [ft]
4
L
' : Length of ø15.88[5/8"] liquid pipe [ft]
5
L
' : Length of ø12.7[1/2"] liquid pipe [ft]
6
L
' : Length of ø9.52[3/8"] liquid pipe [ft]
7
L
' : Length of ø6.35[1/4"] liquid pipe [ft]
8
(kg)
' (oz)
2
2
2.0
71
(kg)
' (oz)
3
3
1.0
35
2.0
71
- 184 -
P192
6.0
6.0
13.2
13.2
)+ (0.2 x L
)
4
5
4
' )+ (2.16 x L
' )
4
5
' +
'
3
4
Amount for the Indoor
Total capacity of
unit
connected indoor
units
(kg)
4
-
27
2.0
28
-
54
2.5
55
-
126
3.0
127
-
144
3.5
145
-
180
4.5
181
-
234
5.0
235
-
273
6.0
274
-
307
8.0
308
-
342
9.0
343
-
411
10.0
412
-
480
12.0
481
-
14.0
' (oz)
4
71
89
106
124
159
177
212
283
318
353
424
494
GB