Introduction; General; Electrical Controls And Wiring - Carrier 58STA070-12 Installation Instruction

Single-stage deluxe induced-combustion 4-way multipoise furnace
Table of Contents

Advertisement

Table 12—Orifice Size* And Manifold Pressure For Gas Input Rate (Continued)
(Tabulated Data Based On 22,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level)
AVG GAS
ALTITUDE
HEAT VALUE
RANGE
AT ALTITUDE
(FT)
(BTU/CU FT)
600
625
9001
650
to
675
10,000
700
725
* Orifice numbers 43 are factory installed
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in improper furnace
operation.
Label all wires prior to disconnection when servicing con-
trols. Wiring errors can cause improper and dangerous
operation.
Step 1—Introduction

GENERAL

These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of the
furnace, and conditioned air is discharged upward. Since this
furnace can be installed in any of the 4 positions shown in Fig. 4,
you must revise your orientation to component location accord-
ingly.

ELECTRICAL CONTROLS AND WIRING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
There may be more than one electrical supply to the furnace.
Check accessories and cooling unit for additional electrical
supplies that must be shut off during furnace servicing.
The electrical ground and polarity for 115-v wiring must be
properly maintained. Refer to Fig. 25 for field wiring information
and to Fig. 45 for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the
control will flash rapidly and prevent the furnace from heating.
The control system also requires an earth ground for proper
operation of the control and flame-sensing electrode.
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the control. (See Fig. 24.) Any shorts of the 24-v wiring during
installation, service, or maintenance will cause this fuse to blow. If
fuse replacement is required, use ONLY a 3-amp fuse. The control
LED will display status code 24 when fuse needs to be replaced.
Proper instrumentation is required to service electrical controls.
The control in this furnace is equipped with a Status Code LED
(Light-Emitting Diode) to aid in installation, servicing, and
troubleshooting. It can be viewed through the sight glass in blower
access door. The furnace control LED is either ON continuously,
SPECIFIC GRAVITY OF NATURAL GAS
0.58
Orifice
Manifold
Orifice
No.
Pressure
No.
43
2.7
43
43
2.5
43
43
2.3
43
43
2.1
43
48
3.7
43
48
3.5
48
38
0.60
0.62
Manifold
Orifice
Pressure
No.
Pressure
2.8
43
2.6
43
2.4
43
2.2
43
2.0
43
3.6
48
rapid flashing, or a code composed of 2 digits. The first digit is the
number of short flashes, the second digit is the number of long
flashes.
For an explanation of status codes, refer to service label located on
blower access door or Fig. 49 and the troubleshooting guide which
can be obtained from your distributor. The furnace control will
store 1 status code for 72 hrs.
See Fig. 53, a brief Troubleshooting Guide.
For Controls With a RED LED
The stored status code will be erased from the control memory, if
115- or 24-v power is interrupted.
1. To retrieve status code, proceed with the following:
NOTE: NO thermostat signal may be present at control, and all
blower-OFF delays must be completed.
a. Leave 115-v power to furnace turned on.
b. Remove outer access door.
c. Look into blower access door sight glass for current LED
status. Do not remove blower access door or terminate
115-v power to control or status code will be lost.
d. BRIEFLY remove insulated terminal wire from the draft
safeguard (DSS) switch until LED goes out (1 to 2 sec),
then reconnect it.
2. When above items have been completed, the LED flashes
status code 4 times. Record this status code for further
troubleshooting.
3. Component self-test will begin. Refer to component TEST
section for complete test sequence.
4. Check LED status.
5. Refer to SERVICE label on front of the blower access door for
more information.
6. Check LED status. If no previous faults in history, control will
flash status code 11.
7. If LED status indicates proper operation, RELEASE
BLOWER ACCESS DOOR SWITCH, reattach wire to "R"
terminal on furnace control board, replace blower access dorr,
and replace burner access door.
0.64
Manifold
Orifice
Manifold
No.
Pressure
2.9
43
3.0
2.6
43
2.7
2.4
43
2.5
2.3
43
2.3
2.1
43
2.2
3.7
43
2.0

Advertisement

Table of Contents
loading

Table of Contents