Gas Piping - Carrier 58STA070-12 Installation Instruction

Single-stage deluxe induced-combustion 4-way multipoise furnace
Table of Contents

Advertisement

FURNACE
RETURN-AIR
SIZE
INLET
Bottom
048135
or
Side(s)
Bottom
Only
Bottom, Sides or
066135
1 Side & Bottom
1 Side Only
Bottom
Only
Both Sides Or
060155
1 Side & Bottom
1 Side Only
*A filter is required for each return-air inlet. Airflow performance included 1-in. washable filter media such as contained in factory-authorized accessory filter rack. To
determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
-- Indicates unstable operating conditions.Table 5—Air Delivery - CFM (With Filter)* (Continued)

GAS PIPING

FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Never purge a gas line into a combustion chamber. Never test
for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of
leaks to check all connections.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning coud result in personal injury,
death, and/or property damage.
Use proper length of pipe to avoid stress on gas control
manifold and a gas leak.
Gas piping must be installed in accordance with national and local
codes. Refer to current edition of NFGC in the U.S., the NSCNG-
PIC in Canada.
Installations must be made in accordance with all authorities
having jurisdiction. If possible, the gas supply line should be a
separate line running directly from meter to furnace.
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed
plumber or gas fitter.
2. When flexible connectors are used, the maximum length
shall not exceed 36 inches (915 mm).
3. When lever handle type manual equipment shutoff valves are
used, they shall be T-handle valves.
4. The use of copper tubing for gas piping is NOT approved by
the state of Massachusetts.
Refer to Table 6 for recommended gas pipe sizing. Risers must be
used to connect to furnace and to meter. Support all gas piping
with appropriate straps, hangers, etc. Use a minimum of 1 hanger
Table 5—Air Delivery - CFM (With Filter)* (Continued)
SPEED
0.1
0.2
High
2090
2010
Med-High
1790
1755
Med-Low
1545
1525
High
2485
2400
Med-High
2195
2150
Med-Low
1880
1850
High
--
--
Med-High
2180
2145
Med-Low
1880
1850
High
--
--
Med-High
2135
2085
Med-Low
1880
1850
High
2465
2430
Med-High
2115
2105
Med-Low
1800
1790
High
--
--
Med-High
2155
2135
Med-Low
1800
1790
High
--
--
Med-High
2140
2095
Med-Low
1800
1790
EXTERNAL STATIC PRESSURE (IN. WC)
0.3
0.4
0.5
0.6
1930
1835
1710
1590
1705
1640
1550
1465
1500
1450
1380
1315
2310
2215
2110
2000
2090
2000
1920
1825
1820
1780
1715
1635
2385
2305
2195
2085
2060
2010
1945
1865
1820
1780
1715
1635
2245
2155
2055
1940
2035
1975
1895
1795
1820
1780
1715
1635
2375
2305
2230
2110
2075
2030
1980
1910
1770
1735
1695
1640
2375
2285
2200
2105
2095
2040
1975
1895
1770
1735
1695
1640
2260
2180
2085
1975
2040
1975
1890
1810
1770
1735
1695
1640
every 6 ft. Joint compound (pipe dope) should be applied sparingly
and only to male threads of joints. Pipe dope must be resistant to
the action of propane gas.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
If local codes allow the use of a flexible gas appliance
connector, always use a new listed connector. Do not use a
connector which has previously served another gas appliance.
Black iron pipe shall be installed at the furnace gas control
valve and extend a minimum of 2 in. outside the furnace.
FURNACE OVERHEAT HAZARD
Failure to follow this caution may result in unit component
damage.
Connect gas pipe to gas valve using a backup wrench to avoid
damaging gas controls and burner misalignment.
An accessible manual equipment shutoff valve MUST be installed
external to furnace casing and within 6 ft of furnace. A 1/8-in. NPT
plugged tapping, accessible for test gauge connection, MUST be
installed immediately upstream of gas supply connection to
furnace and downstream of manual equipment shutoff valve.
NOTE: The furnace gas valve inlet pressure tap connection is
suitable to use as test gauge connection providing test pressure
DOES NOT exceed maximum 0.5 psig (14-in. wc) stated on gas
control valve. (See Fig. 46.)
Some installations require gas entry on right side of furnace (as
viewed in upflow.) (See Fig. 21a.)
Install a sediment trap in riser leading to furnace as shown in Fig
21b. Connect a capped nipple into lower end of tee. Capped nipple
should extend below level of furnace gas controls. Place a ground
joint union between furnace gas control valve and exterior manual
equipment gas shutoff valve. A 1/8-in. NPT plugged tapping,
17
0.7
0.8
0.9
1.0
1470
1335
1025
835
1360
1210
945
785
1215
1005
855
670
1880
1725
1535
1355
1720
1565
1405
1255
1540
1415
1290
1160
1960
1825
1670
1465
1765
1660
1515
1325
1540
1415
1290
1160
1825
1695
1555
1385
1685
1565
1445
1265
1540
1415
1290
1160
2000
1865
1725
1545
1830
1725
1590
1425
1570
1465
1345
1225
1995
1870
1730
1570
1790
1685
1550
1400
1570
1465
1345
1225
1865
1740
1605
1455
1705
1595
1480
1325
1570
1465
1345
1225

Advertisement

Table of Contents
loading

Table of Contents